5.16
IGBT over-strong current protection diagnosis and solution
Recommended parts to prepare:
• Faulty IGBT
• Faulty outdoor PCB
Troubleshooting and repair:
Shut off the power supply and
turn it on 2 minutes later.
Is it still displaying
the error code?
YES
Replace the outdoor main
PCB.
The unit is operating normally.
NO
Содержание MISSION2 3D INVERTER Series