Air-cooled modular chiller unit
76
14) Ambient temperature sensor malfunction
Ambient temperature sensor
malfunction.
Inform the customer service
center.
PCB mistakes to alarm.
The circuit of ambient temperature
sensor is broken.
Replace PCB.
Replace temperature sensor.
The circuit of ambient temperature
sensor is shorten.
Replace temperature sensor.
The joint of ambient temperature
sensor is loose.
Fixed joint.
No
Yes
Yes
Yes
Yes
Yes
No
No
No