Air-cooled modular chiller unit
Connection Method 2:
Air-cooled Modular units:Max 16 units(The network address is unique)
LONWORKS
NET WORK
LSQ-LONWORKS
BMS SYSTEM
RS485(P Q E)
Caution
This system adopts the manner of shared network variable to manage A/C system, which cannot access the
appointed A/C within central A/C system, until the co-responding network variable is modified to the one that
is intended to access. This device consists of one transceivers (the following called Main controller for short).
Main controller is responsible for querying and setting of 16 sets Air-cooled Modular units with addresses of
0~15 .
1
.6.6 NetWork Variables of setting main controller
NO
Name
Name
2:4800bps
Initial value=2
Address
Type
nciUARTBaud SNVT_count
SNVT_count
SNVT_count
nciType
NciCtrl_ Addr
Network
variable name
Network
variable type
Data definition
Descriptions
1
2
3
Gateway type, need to be set as the actual condition.
The initial value is 0
Used for setting the baud rate of Rs485 port, and the
gateway is used 4800 baud rate.
The value is fixed to be 2.
The gateway address of the Air-cooled Modular unit
system. “Address” must be set the corresponding
value, as displayed in Table A
.
The initial value is 240.
0
:
KJR-120A/MBE
1
:
KJR-08B/BE
Initial value=0
240,241...255
Initial value=240
Содержание MCCDH30A-TA3SL
Страница 17: ...Air cooled modular chiller unit 17 30kW module 1865 874 317 Front view Left view Top view 4 Dimension...
Страница 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Страница 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Страница 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Страница 41: ...Air cooled modular chiller unit 41 185 kW module...
Страница 46: ...Air cooled modular chiller unit 46 130 kW module...
Страница 48: ...Air cooled modular chiller unit 60 200kW module...
Страница 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Страница 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...