Air-cooled modular chiller unit
83
If the spaces mentioned above cannot be met, the air passing from the unit to the coils may be restricted, or
back flow of air discharge may occur, and the performance of the unit may be affected, or the unit may fail to
operate.
No
Model
Max unit combined
quantity
L(mm)
M(mm)
N(mm)
1
2
3
MCCH30A-TA3SL
1
≥
600
≥
300
≥
300
4
MCDH30A-TA3SL
1
≥
600
≥
300
≥
300
5
6
7
MCCH65A-SA3L
16
≥
600
≥
300
≥
300
MCCD65A-SA3L
16
≥
600
≥
300
≥
300
MCCH130A-SA3L
8
≥
600
≥
300
≥
300
MCCH185A-SA3
5
≥
600
≥
300
≥
300
MCCH250A-SA3T
8
≥
600
≥
300
≥
300
1
.1.3 Installation Foundation
The unit should be located on the horizontal foundation, the ground floor or the roof which can bear
operating weight of the unit and the weight of maintenance personnel. Refer to the operating weight
parameters in specification table.
If the unit is located so high that it is inconvenient for maintenance personnel to conduct maintenance,
the suitable scaffold can be provided around the unit.
The scaffold must be able to bear the weight of maintenance personnel and maintenance facilities.
The bottom frame of the unit is not allowed to be embedded into the concrete of installation foundation.
Содержание MCCDH30A-TA3SL
Страница 17: ...Air cooled modular chiller unit 17 30kW module 1865 874 317 Front view Left view Top view 4 Dimension...
Страница 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Страница 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Страница 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Страница 41: ...Air cooled modular chiller unit 41 185 kW module...
Страница 46: ...Air cooled modular chiller unit 46 130 kW module...
Страница 48: ...Air cooled modular chiller unit 60 200kW module...
Страница 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Страница 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...