Air-cooled modular chiller unit
Table of diameter parameters of main inlet and outlet pipes for 130kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
130×1
DN65
130×5
DN125
130×2
DN100
130×6
DN150
130×3
DN100
130×7
DN150
130×4
DN125
130×8
DN200
Table of diameter parameters of main inlet and outlet pipes for
kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
200×1
DN80
200×4
DN150
200×2
DN100
200×5
DN200
200×3
DN125
Table of diameter parameters of main inlet and outlet pipes for250kW module
Unit model x quantity
Total inlet and outlet water
pipe diameter
Unit model x quantity
Total inlet and outlet water
pipe diameter
250×1
DN100
250×5
DN150
250×2
DN100
250×6
DN200
250×3
DN125
250×7
DN250
250×4
DN150
250×8
DN250
Please pay attention to the following items when installing multiple modules:
● Each module corresponds to an address code which cannot be repeated.
● Main water outlet temperature sensing bulb, target flow controller and auxiliary electric heater are under
control of the main module.
● One wired controller and one target flow controller are required and connected on the main module.
● The unit can be started up through the wired controller only after all addresses are set and the
aforementioned items are determined. The wired controller is ≤50m away from the outdoor unit.
1
.2.9 Chilled water flow
Minimum chilled water flow
The minimum chilled water flow is shown in the below table.
If the system flow is less than the minimum unit flow rate, the evaporator flow can be recalculated, as shown
in the diagram.
Evaporator
Recirculation
For minimum chilled water flow rate
Fig. 4-2
For maximum chilled water flow rate
Evaporator
Recirculation
Maximum chilled water flow
The maximum chilled water flow is limited by the permitted pressure drop in the evaporator. It is provided in
the below table.
If the system flow is more than the maximum unit flow rate, bypass the evaporator as shown in the diagram
to obtain a lower evaporator flow rate.
Содержание MCCDH30A-TA3SL
Страница 17: ...Air cooled modular chiller unit 17 30kW module 1865 874 317 Front view Left view Top view 4 Dimension...
Страница 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Страница 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Страница 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Страница 41: ...Air cooled modular chiller unit 41 185 kW module...
Страница 46: ...Air cooled modular chiller unit 46 130 kW module...
Страница 48: ...Air cooled modular chiller unit 60 200kW module...
Страница 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Страница 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...