Air-cooled modular chiller unit
55
9.3.
MCCH130A-SA3L
Cooling:
Chilled water
outlet temp.
Ambient temp.(
℃
)
21.00
25.00
30.00
35.00
40.00
46.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(
℃
)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
5.00
145.54
35.93
137.04
37.05
129.29
38.19
122.20
39.37
114.50
41.34
105.34
43.41
6.00
150.46
36.49
141.54
37.62
133.40
38.78
125.97
39.98
118.16
41.98
108.83
44.08
7.00
155.71
37.24
146.34
38.39
137.80
39.58
130.00
40.80
122.07
42.84
112.55
44.98
8.00
160.52
38.35
150.72
39.54
141.79
40.76
133.64
42.02
125.62
44.13
115.95
46.33
9.00
165.05
38.73
154.83
39.92
145.52
41.16
137.02
42.43
128.94
44.55
119.14
46.78
10.00
171.31
39.31
160.55
40.52
150.75
41.78
141.82
43.07
133.59
45.22
123.57
47.48
11.00
176.08
39.69
164.87
40.92
154.66
42.19
145.36
43.49
137.08
45.67
126.93
47.95
12.00
180.11
40.28
168.49
41.52
157.91
42.81
148.27
44.13
139.97
46.34
129.75
48.65
13.00
183.33
40.60
171.33
41.85
160.42
43.15
150.49
44.48
142.22
46.71
131.98
49.04
14.00
187.89
40.88
175.43
42.14
164.11
43.45
153.80
44.79
145.50
47.03
135.17
49.38
15.00
190.30
41.08
177.52
42.35
165.90
43.66
155.34
45.01
147.11
47.26
136.81
49.63
Note:
The inlet/outlet water temperature difference is 5
℃
.
Содержание MCCDH30A-TA3SL
Страница 17: ...Air cooled modular chiller unit 17 30kW module 1865 874 317 Front view Left view Top view 4 Dimension...
Страница 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Страница 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Страница 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Страница 41: ...Air cooled modular chiller unit 41 185 kW module...
Страница 46: ...Air cooled modular chiller unit 46 130 kW module...
Страница 48: ...Air cooled modular chiller unit 60 200kW module...