Air-cooled modular chiller unit
5
2. Features
1). Low ambient temperature cooling function (Available for MCC(D)H30A-TA3SL,
MCC(D)H65A-SA3L,
MCCH130A-SA3L)
The ambient temperature is down to -10
℃
in cooling mode, and heating down to -10˚C ambient by added
one board (see picture1). Wide ambient temperature range are available by adjustable address between
different conditions to meet different requirements.
Mode
Ambient temp.
Cooling
Normally
(
S8 address OFF
)
10~46
℃
※
Low temp. (S8 address ON)
-10~46
℃
Heating
-10~21
℃
2). Wide range of outlet water temperature (For the module with KJR-120A/MBE)
Cooling: 5~17˚C (Set in factory), 0~17˚C can be available by switch the S5 on PCB, the antifreeze must be
put into pipeline.
Heating: 40~50˚C (Set in factory), 22~50˚C can be available by switch the address.
Mode
Outlet water temp.
Cooling(S5 address)
Normally(OFF)
5~17
℃
Low water temp.(ON)
0~17
℃
Heating(S4 address)
Normally(OFF)
40~50
℃
Low water temp. (ON)
22~50
℃
3).Built-in hydraulic module (Available for MCC(D)H30A-TA3SL)
The unit built-in hydraulic module to simplified installation, save space and beautification appearance,
simultaneous effectively reduce installation costs and covering area.
Содержание MCCDH30A-TA3SL
Страница 17: ...Air cooled modular chiller unit 17 30kW module 1865 874 317 Front view Left view Top view 4 Dimension...
Страница 37: ...Air cooled modular chiller unit 37 MCCH65A SA3L...
Страница 38: ...Air cooled modular chiller unit 38 MCCD65A SA3L...
Страница 40: ...Air cooled modular chiller unit 40 MCCH130A SA3L...
Страница 41: ...Air cooled modular chiller unit 41 185 kW module...
Страница 46: ...Air cooled modular chiller unit 46 130 kW module...
Страница 48: ...Air cooled modular chiller unit 60 200kW module...
Страница 78: ...Air cooled modular chiller unit 78 65kW module 130kW module...
Страница 153: ...Air cooled modular chiller unit Fig 4 70 Fig 4 71...