Chapter 9 User interfaces
Universal inputs
(Frequency mode
1/2)
Freq
(1/2)
Filter time Minimum signal length for the signal detection [ms]
Decay
Temporal function in the measurement cycle
Off
Decay deactivated
min
The minimum of the last x measurement
values is recorded.
max
The maximum of the last x measurement
values is recorded.
avg
The arithmetic mean of the last x
measurement values is recorded.
med
The median of the last x measurement
values is recorded.
rms
The root mean square of the last x
measurement values is recorded.
Time
Decay period. Up to a maximum of 60 measurement
valuescan be used for the calculation (e.g. 1 channel:
60 measurement values; ... 4 channels:
15 measurement values each). To calculate the number
of measurement values that are taken into account,
refer to "Example to clarify the record interval,
measurement cycle and burst interval in conjunction
with the decay" in chapter "Basic setting" on page 73.
Hold
Hold the last valid measurement value for x
measurement cycles
Off
Function deactivated
1-5
Number of measurement cycles for which
the measurement value is held until the
error value is issued
On
In the event of an error, the last valid
measurement value is held until a new
valid measurement value is present.
Rev. 01
63
Содержание myDatalogNANO Ex
Страница 2: ......
Страница 8: ......
Страница 9: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 01 9 ...
Страница 10: ...2 1 Declaration of conformity Appendix 10 Rev 01 ...
Страница 11: ...Chapter 2 Declaration of conformity Rev 01 11 ...
Страница 12: ......
Страница 24: ......
Страница 52: ......
Страница 78: ......
Страница 86: ......
Страница 92: ......
Страница 104: ......
Страница 107: ...Chapter 17 Document history Chapter 17 Document history Rev Date Changes 01 10 09 2013 First version Rev 01 107 ...
Страница 108: ......
Страница 110: ......