7.4.4.1 Digital modes (digital, day counter, pulse counter, frequency, PWM)
If a universal input is operated in one of the digital modes, a switch contact can be connected
directly to the universal input without an additional energy supply.
Note: Due to the input circuit (see following schematic diagram), a cross current of 4,9µA is
generated for every universal input, that is operated in one of the digital modes, when the
switch contact is open. This increases the energy requirement and reduces the device
operating time.
Schematic diagram: Universal input in one of the digital modes
1 myDatalogNANO Ex
2 Equivalent circuit diagram for the switch
contact
V
CPU
3,6V
I
out max
68,97µA
R
load max
59k3
C
load max
200nF
General
Low
<2,3V
High
>2,4V
PWM
Measurement
range
1...99%
f
max
25Hz (at 50%
pulse duty factor)
Minimum pulse
length
20ms
Frequency
Measurement
range
1...25Hz (at 50%
pulse duty factor)
Day and
pulse counter
Minimum pulse
length
20ms
50
Rev. 01
Содержание myDatalogNANO Ex
Страница 2: ......
Страница 8: ......
Страница 9: ...Chapter 2 Declaration of conformity Chapter 2 Declaration of conformity Rev 01 9 ...
Страница 10: ...2 1 Declaration of conformity Appendix 10 Rev 01 ...
Страница 11: ...Chapter 2 Declaration of conformity Rev 01 11 ...
Страница 12: ......
Страница 24: ......
Страница 52: ......
Страница 78: ......
Страница 86: ......
Страница 92: ......
Страница 104: ......
Страница 107: ...Chapter 17 Document history Chapter 17 Document history Rev Date Changes 01 10 09 2013 First version Rev 01 107 ...
Страница 108: ......
Страница 110: ......