Page 57
Setting Sensor Parameters
optoNCDT 1900 / Profinet
Timestamp
32 Bit
x
Digital value
[0; 4294967295]
t
=
x
1
1000
t
Time stamp in µs
[0; 1h11m34.967s]
Unlinearized
center of gravity
18 Bit
x
Digital value
[0; 262143]
US
=
x
100
262143
CG
Center of gravity in %
[0; 100]
Measurement
frequency
18 Bit
x
f
Digital value
Frequency in Hz
[2500; 100000]
f
=
x
10
State information transferred in the distance value
Distance value
Description
262076
There is no peak present
262077
Peak is before measuring range (MR)
262078
Peak is after measuring range (MR)
262080
Measurement value cannot be evaluated
262081
Peak is too wide
262082
Laser is off
i
The sensor sends the cyclic process data in little-endian format. The acyclic requirements data is also in little-endian format;
records are read as little-endian and must also be written as little-endian. If the PLC uses the big-endian format, the byte order
must be swapped.