background image

11

ENGLISH

30 S

25  HS

15 H - HS

rpm
rpm
rpm

Natural  gas

(G20)

56
51
48

LPG

propane  (G31)

52
48
46

Maximum CH fan rpm

Gas valve calibration
• Power the boiler.
• Open the gas tap.
• Turn the function selector to OFF/RESET (digit “--”).
• Pull off the domestic hot water temperature selector knob (7, Fig. 12.1) and

the domestic hot water function selector knob (6, Fig. 12.1).

• Press the combustion analysis  button CO.
• Wait for the burner to ignite. “CO” is displayed on the digital display and the

boiler works at maximum heating power. The flue cleaner function remains
active for a maximum of 15 min; if a delivery temperature of 95°C is reached,
the burner switches off. It is re-ignited when this temperature falls below
75°C.

• Remove the plug and insert the fumes analysis probe.
• Turn the max. heating trimmer clockwise until it reaches the maximum fan

rpm (see table).

• Check the CO

2

 value: if the value does not match that indicated in the

table, turn the maximum gas valve adjustment screw.

• Turn the max. heating trimmer anti-clockwise until it reaches the minimum

fan rpm (see table).

• Check the CO

2

 value: if the value does not match that indicated in the

table, turn the minimum gas valve adjustment screw.

• Turn the max. heating trimmer to the maximum heating fan rpm (see table)

12.4 - Boiler configuration
The electronic board contains a series of jumpers (JP4) that can be used
to configure the boiler; access these by loosening the fasteners B (Fig. 7.2)
and removing the control panel cover A (Fig. 7.2) after turning off the main
switch.
JUMPER IN POSITION 1:
pre-selection  of  the  most  suitable  heating  temperature  adjustment  field
according to the type of system.
Jumper not inserted - case A
Standard system 40-80°C
Jumper inserted - case B
Floor system 20-45°C.
The boiler has been factory-configured for standard systems.

For S models (Fig. 12.14):
JUMPER IN POSITION 2: (unused)
JUMPER IN POSITION 3: (unused)
JUMPER IN POSITION 4: (unused)
JUMPER IN POSITION 5: COMBINED
JUMPER IN POSITION 6: (unused)

For  H-HS  models  (Fig.  12.15):
JUMPER IN POSITION 2: (water tank with probe)
JUMPER IN POSITION 3: (water tank with thermostat)
JUMPER IN POSITION 4: (unused)
JUMPER IN POSITION 5: (unused)
JUMPER IN POSITION 6: (unused)

The boiler HS is supplied standard with the jumper in position 2 (water
tank with probe); if you wish to use an external water tank with thermostat,
move this jumper from position 2 to position 3 (case C, Fig. 12.15).

ATTENTION
If the boiler is not connected to an external water tank, put the jumper in
position 3.

13 - SETTING THE THERMOREGULATION

Heat adjustment only works with the external probe connected, therefore,
after installation, connect the external probe to the relative connections on
the boiler terminal board.
This enables the THERMOREGULATION function.

Selecting the offset heating curve (Fig. 13.1)
The offset heating curve maintains a theoretical ambient temperature of 20°C
at external temperatures ranging from +20°C to -20°C. The choice of the curve
depends on the rated minimum external temperature (on the geographical
area, therefore) and the rated delivery temperature (on the type of system,
therefore) and must be carefully calculated by the fitter using the following
formula:

Tshift = 30°C standard systems

25°C floor systems

If the calculation generates an intermediate value between two curves, choose
the nearest offset heating curve to that value.
E.g.: if the value obtained by the calculation is 1.3, it lies between curve 1 and
curve 1.5. In this case, select the nearest curve, i.e.: 1.5.
Select KT by turning the trimmer located under the domestic hot water tempe-
rature knob (A, Fig. 13.2).
The settable values of KT are:
• standard system: 1,0-1,5-2,0-2,5-3,0
• floor system: 0,2-0,4-0,6-0,8
Type of heat request
If an ambient thermostat is connected to the boiler (parameter 51 = 0 -
manufacturer’s default setting) (Fig. 13.3)
The ambient thermostat makes a heat request when its contact closes, while
it stops it when its contact opens. Though delivery temperature is automatically
calculated  by  the  boiler,  the  user  may  manually  override  it.  By  modifying
HEATING on the user interface (C, Fig. 13.2), the HEATING SET POINT will
no longer be available but just a value that can be set from +5 to -5°C as
required. Modifications to this value do not directly change delivery tempera-
ture but affect the calculation made to automatically determine its value by
modifying the reference temperature of the system (0 = 20°C).

If a programmable timer is connected to the boiler, set parameter 51 =
1 (this parameter can only be modified from the remote control unit)
(Fig. 13.4)
When the contact is closed, the heat request is made by the delivery probe on
the basis of the external temperature in order to maintain the rated ambient
temperature at the DAY level (20 °C). When the contact opens, it does not
stop the heat request but reduces (parallel shift) the temperature curve to the
NIGHT level (16 °C).
This activates the night mode.

Though delivery temperature is automatically calculated by the boiler, the
user may manually override it.
By modifying HEATING on the user interface (C, fig. 13.2), the HEATING
SET POINT will no longer be available but just a value that can be set from
+5 to -5°C as required.
Modifications to this value do not directly change delivery temperature but
affect the calculation made to automatically determine its value by modifying
the reference temperature of the system (0 = 20°C for DAY level; 16°C for
NIGHT level).

14 - ADJUSTMENTS

The boiler has already been factory-adjusted by the manufacturer. If a new
adjustment is required, for example, after extraordinary maintenance, replacing
the gas valve or converting from natural gas to LPG, proceed as follows.

Maximum and minimum power, maximum heating and slow start must
be adjusted in the indicated sequence by qualified staff.

• Power the boiler.
• Turn the function selector to OFF/RESET (digit “--”).
• Pull off the 3 function buttons (domestic hot water A, command B and

heating C, Fig. 13.2).

• Turn the trimmers in the following sequence and adjust them until their

values correspond with those indicated in the table:
1. Max (maximum fan rpm)
2. Min (minimum fan rpm)
3. Max risc. (maximum heating fan rpm)
4. Slow start LA (set to 3.7=3700 rpm)

Calibration does not switch on the boiler.
When the trimmers are turned the value expressed in thousands (e.g..
2.5=2500 rpm) is indicated on the 2-digit display).
Slow start LA must be adjusted after calibrating all the other trimmers.

%
%
%

Natural  gas

(G20)

8,5
8,5
9,0

LPG

propane  (G31)

10,0
10,0
10,0

CO

2

 max

30 S

25 HS

15 H - HS

30 S

25  HS

15 H - HS

%
%
%

Natural  gas

(G20)

9,0
9,0
9,0

LPG

propane (G31)

10,0
10,0

10,0

CO

2

 min

KT =

Nominal delivery T. - Tshift

20 - min. rated external T.

30 S

25  HS

15 H - HS

rpm
rpm

rpm

Natural  gas

(G20)

15
14
15

LPG

propane  (G31)

15
14
14

Minimum fan rpm

30 S

25  HS

15 H - HS

rpm
rpm
rpm

Natural  gas

(G20)

63
51
48

LPG

propane  (G31)

63
48
46

Maximum  fan rpm

Содержание procon gwb smartline

Страница 1: ...er and user manual ES Manual de instalaci n y uso PL Instrukcja obs ugi instalacji i konserwacji RO Manual de instalare si utilizare DK Installations og brugervejledning FR Manuel d installation et d...

Страница 2: ...o al usuario como al instalador PL RO Acest manual contine date si informatii atat pentru utilizator cat si pentru instalator Si anume Capitolele intitulate Instalarea cazanului Conectare la reteaua d...

Страница 3: ...display and disconnect the electricity supply by turning off the two position system switch before cleaning It is forbidden to modify the safety or adjustment devices without the manufacturer s permis...

Страница 4: ...e the supplied power cable to connect the boiler to the mains power supply Connect the ambient thermostat and or external programmable timer clock as shown in the electrical diagram on page 75 When re...

Страница 5: ...towards the boiler Non insulated fumes outlet ducts are potential sources of danger The boiler automatically adapts ventilation according to the type of installation and the length of the duct Do not...

Страница 6: ...ity Gas pressure Natural gas pressure G20 LPG pressure G31 Hydraulic connections CH input output Water tank delivery return Gas input Boiler dimensions and weight Height Width Depth Weight Fan perform...

Страница 7: ...me exhaustion and air suction concentric pipe Diameter Max lenght Loss for a 90 45 bend Hole in wall diameter Fume exhaustion and air suction concentric pipe Diameter Max lenght Loss for a 90 45 bend...

Страница 8: ...an ProCon Smartline 30 S Number of main burner nozzles Gas diaphragm CH maximum gas capacity DHW maximum gas capacity CH minimum gas capacity DHW minimum gas capacity Fan speed at slow start Maximum s...

Страница 9: ...he domestic hot water in the water tank turn the temperature selector clockwise to increase and anticlockwise to decrease The adjustment range lies between 35 and 60 C When choosing the temperature bo...

Страница 10: ...er circuit should only be considered if a water tank is installed case C accessory available on request 12 1 A green indicator LED boiler status 12 6 12 7 12 8 B red indicator LED fault 12 9 12 10 12...

Страница 11: ...ating curve to that value E g if the value obtained by the calculation is 1 3 it lies between curve 1 and curve 1 5 In this case select the nearest curve i e 1 5 Select KT by turning the trimmer locat...

Страница 12: ...the board generates an alarm If a fault develops during the combustion analysis phase perform the release procedure as follows Turn the function selector 6 to then to and then move it to the required...

Страница 13: ...mes To exit and return to the current operating mode press and release the P button OPERATING MODES Each channel C1 C2 has 3 different modes of operation Automatic using the stored ON OFF settings ON...

Страница 14: ...ik 22 G wny wymiennik ciep a 23 Mieszalnik 24 Wentylator 25 Dolny zaw r odpowietrzaj cy 26 Pompa cyrkulacji 27 Prze cznik przep ywowy S 28 Wymiennik ciep a gor cej domowej wody S 29 Silnik zaworu tr j...

Страница 15: ...dpowietrzaj cy U Cyrkulator V Wymiennikciep agor cejdomowejwody W Zaw r tr jdro ny X Regulator przep ywu Y Prze cznik przep ywowy RO Circuit hidraulic S RO Circuit hidraulic S RO Circuit hidraulic S R...

Страница 16: ...powietrzaj cy Q Separator wody powietrza R Zaw r r cznego odpowietrzania S Dolny zaw r odpowietrzaj cy T Cyrkulator U Silnik zaworu tr jdro nego V Zbiornik wody dost pny na danie RO Circuit hidraulic...

Страница 17: ...71 ProCon Smartline ProCon Smartline S...

Страница 18: ...72 ProCon Smartline ProCon Smartline HS...

Страница 19: ...tank thermostat M2 M4 water tank probe terminal strip HS External probe remote control M4 External probe remote control V1 V2 Gas valve operator P Pump W D S Water pressure switch P1 Domestic hot wat...

Страница 20: ...dere I E 2 Electrod de relevare flacara F Siguranta 3 15A F rapida F1 F2 Siguranta 3 15A T intarziata DFS Fluxostat sanitar S JP5 Jumper preselectare config centrala poz 5 pentru S JP2 Jumper preselec...

Страница 21: ...ea termostatului de ambient si sau RO Conectarea termostatului de ambient si sau RO Conectarea termostatului de ambient si sau RO Conectarea termostatului de ambient si sau a programatorului or a prog...

Страница 22: ...i wymagany jest wy szy s up wody dost pny na danie jest zestaw cyrkulatora wysokiego s upa wody wykresy 3 4 prima velocita pierwsza pr dko seconda velocita druga pr dko terza velocita trzecia pr dko R...

Страница 23: ...ons in mm ES Medidas en mm PL Wymiary w mm RO Dimensiuni in mm DK Dimensioner i mm FR Dimension en mm EN H Water gas ES H Agua gas PL H Woda gaz RO H Apa gaz DK H Vand gas FR H Gaz eau A B 30 S 452 5...

Страница 24: ...ax 50 cm ES A Salida trasera B M x 50 cm PL A Tylny wylot B Maks 50 cm RO RO RO RO RO A Supapa posterioara B Max 50 cm DK A Bagerste udtag B Max 50 cm FR A Sortie arri re B Maxi 50 cm C13 C13 C53 C53...

Страница 25: ...evacuare fum aspirare aer C Tuburi separate pentru evacuare fum aspirare aer D Adaptor 60 80 DK A R ggasaftr k til indtag i omgivelser B Balanceret aftr k til r ggasudtag luftindtag C Splitkanal til r...

Страница 26: ...O RO RO RO RO A Curbe de termoreglare B Corectarea curbei de temperatura C Paralele diminuare grad confort D Temperatura de pe tur C E Temperatura externa C F T80 Set point temperatura maxima de incal...

Страница 27: ......

Отзывы: