10
ProCon Smartline
Code
AL10
AL20
AL21
AL29
AL60
AL60
AL71
AL73
AL28
AL26
AL79
AL41
AL40
AL34
AL52
AL55
AL91
Description of alarm
Ignition attempts finished (no flame/condensate present)
Limit thermostat fault
Low temperature thermostat/condensate pump safety
device fault
Fumes probe overtemperature
Domestic hot water probe fault (S)
Water tank probe fault (H-HS)
Delivery probe fault (open/short circuit)
Return probe fault (open/short circuit)
Return/delivery probe differential fault
Return over temperature
Delivery over temperature / return-delivery probe
differential fault
System water pressure low
System water pressure low (after 10 minutes)
Fan tacho fault
Generic electronic fault
No boiler mode configuration fault (corresponding
jumper absent)
Clean primary exchanger (call the technical
assistance service)
Status
Block
Block
Block
Block
See dedicated
section
Block
Stop
Stop
Block
Block
Block
Stop
Block
Block
Block
Block
Signal
For S models only
12.3
DHW mode
CH mode
12.4
12.5
1 - Green indicator LED - flame present
2 - Digital display
3 - Red fault LED
4 - Digital clock
5 - Heating water temperature selector
6 - Function selector
7 - Domestic hot water temperature selector *
8 - Water gauge
* The parts of manual referring to the domestic hot water circuit should only be
considered if a water tank is installed, case C (accessory available on request)
12.1
A green indicator LED
boiler status
12.6
12.7
12.8
B red
indicator
LED fault
12.9
12.10
12.11
12.12
12.16
!"#
!$%
&
"
12.17
• Move the function selector to the desired position.
In case of frequent pressure drops, call in the Technical Service Centre.
Only for S.: AL60 fault
The boiler works regularly but does not ensure the stability of the hot water
temperature which, however, is delivered at a temperature of approximately
50°C.
Contact the Technical Assistance Centre.
Fault code 91
The boiler has a self-diagnosis system which, on the basis of the hours totalised
in particular operating conditions, signals the need for maintenance or cleaning
of the primary exchanger (alarm code 91). After cleaning using the kit supplied
as an accessory, reset the hour counter as follows:
- disconnect the mains power supply
- pull out handle A (Fig. 12.17)
- switch on the boiler by pressing and holding down button B (Fig. 12.17) for
at least 4 seconds
- to check the counter has been reset, switch the boiler off and back on
again; after all the digit segments have lit up, the counter value will be
displayed.
To check the number of hours, multiply the value by 100 (e.g.: value displayed
18 = 1800 hours totalised – value displayed 1= 100 hours totalised).
N.B.: perform the counter reset procedure every time the primary exchanger
is thoroughly cleaned or replaced.
1
2
3
8
7
6
5
4