MH THYROMAT-BDC Скачать руководство пользователя страница 78

 

U

U

s

s

e

e

r

r

 

 

M

M

a

a

n

n

u

u

a

a

l

l

 

 

 

 

 

 

Revision 8.6  

SECTION 5 : COMMISSIONING

 

72 

g) 

Move the cabin joystick to Notch 1 Hoisting  

h) 

Measure the stator and rotor voltages between phases at the motor terminals 

i) 

Confirm that the Stator/Rotor voltage ratio falls  10% of name plate 

NOTE 

This  test  may  only  be  performed  for 
periods of approximately 10 seconds at the 
time  since  the  Thyromat  drive  will  trip  on 
motor stall, if it remains for longer periods 
in Notch 1. 

 

Analyzing the results: 

When  the  above  mentioned  voltage  ratio  falls  within  the  reco  10%  deviation  the  test  is 
considered  successful,  and  the  next  test  must  now  be  performed.    When  such  ratio  is  out  the 
recommended deviation, one needs to verify why this is the case. 

In the case of an upgraded installation it may be that the motor may have been rewound previously and 
its  characteristics  have  changed  slightly,  if  the  deviation  is  too  great,  it  may  be  possibly  that  the  Rotor 
connections have been changed from Y to 

∆ or vice-versa.  In this case the motor may not perform well 

under full load conditions and it may be necessary to replace it with a standby spare motor. 

Under  a  great  discrepancy  on  the  rotor  voltage,  the  rotor  resistance  which  was  calculated  around  the 
motor  name  plate  values  is  going  to  be  inadequate  too  and  this  needs  to be  taken  in  consideration  as 
well. 

Consult MH Automation for advice in the event that the results are out of acceptable boundaries. 

Step 10

 

Perform locked Rotor test (Closed rotor circuit) (this test should only be performed if the test mentioned 
in Step 8 is successful). 

a) 

Repeat step by step all the instructions referred to in Step 9 (a) to (g). 

h) 

Measure the stator voltages between phases.  The supply voltage must remain within 90% of 
its rated value, preferably > 95%.  Look out for any major phase imbalances.  

i) 

Measure the stator currents per phase.  These currents should be fairly balanced. 

j) 

Measure the rotor voltages at the motor terminals between phases. 

k) 

Measure all three rotor currents (at the motor terminals) 

l) 

Assuming  that  there  are  no  major  unbalances  in  either  rotor  voltages  or  currents,  take  the 
average values of both and apply them to the formula below 

Motor kW = Rotor volts x Rotor amps / 605 

The  resultant  kW  for  a  maximum  stall  voltage  of  80%  and  a  Rotor  resistance  of  0,36k  should  be 
approximately the same as the kW which the system has been designed for. 

 

Содержание THYROMAT-BDC

Страница 1: ......

Страница 2: ...PRINCIPLE OF OPERATION 14 2 5 1 Control Box 15 2 5 2 Control Card 15 2 5 3 Relay Card 16 2 5 4 Phase Shifter Card 16 2 5 5 Snubber Card 16 2 5 6 Control Panel 16 2 6 CONTROL SYSTEM SPECIFICATIONS 17 2...

Страница 3: ...Class 31 3 2 4 Notch 1 32 3 2 5 Notch 2 32 3 2 6 Notch 3 32 3 2 7 Hoist Plugging 32 3 2 8 Hoist Plugging V 33 3 2 9 Lower Plugging V 34 3 2 10 Brake Release I 34 3 2 11 Hoist Start Volt 34 3 2 12 Sto...

Страница 4: ...l Signals 47 3 4 21 Plug Reduced SP 48 3 4 22 Notches1 2 3 Smooth Prfl 48 3 4 23 Brake Plug Soft 49 3 4 24 Load Defaults 49 3 5 TORQUE APPLICATION PARAMETER LIST 50 3 6 PARAMETER DESCRIPTIONS TORQUE 5...

Страница 5: ...Triac Outputs Control Panel Board 67 4 4 5 Motor Current Inputs 68 5 COMMISSIONING 5 1 GENERAL 69 5 2 PREPARATION 69 5 3 COMMISSIONING PROCEDURES 70 5 4 HOIST OPERATIONS 75 5 4 1 Hoisting 75 5 4 2 Low...

Страница 6: ...rspeed 90 6 8 10 Motor Stall 91 6 8 11 Input Phases 91 6 8 12 Plugging Timeout 91 6 8 13 Joystick Error 92 6 8 14 RFB Current Loss 92 6 8 15 Not in Neutral 93 6 8 16 Drive Level 93 6 8 17 Power ON Tes...

Страница 7: ...Changed and added Loss of Phase Current Feedback Stack Temp Overload Trip H Loss of Torque Plugging Timeout 6 All Page numbering has been changed due to revision changes Section 6 begins at page 76 t...

Страница 8: ...otor immediately at start of a hoisting cycle This parameter sets up the minimum voltage applied as a percentage of the supply voltage to the motor immediately at start of a hoisting cycle 3 35 3 2 13...

Страница 9: ...remain active 6 76 6 8 1 1 st line as the motor loop speed feedback that is essential as the motor loop speed feedback and it is essential 6 76 6 8 1 Possible causes Rfb and current loss RFB CURRT LO...

Страница 10: ...es unbalanced Change 33 to 50 2 18 Table 5 th row Motor overload protection class Delete sentence and add This feature is not yet implemented 2 22 Table M100 STR 22SE 63A STR 22SE 100A 2 27 2 16 Motor...

Страница 11: ...mented 3 14 20 3 1 Version 9_00 Version 10_00 3 19 3 2 17 terminal 4 Terminals 4 and 5 3 21 26 3 3 Version 7_00 Version 8_00 3 25 3 2 18 terminal 4 Terminals 4 and 5 6 35 6 8 4 Overload Trip Add This...

Страница 12: ...tions combined with digital technology and thousands of man hours of engineering and design has resulted in a unique robust and reliable product Designed specifically to operate in the tough environme...

Страница 13: ...oder required o No mechanical modifications needed on motor shaft o No additional installation costs labour and equipment o No maintenance of a tacho required o No need for small control wires in cabl...

Страница 14: ...6 SECTION 1 GENERAL 8 1 1 1 Basic System Diagram The system s simplicity is illustrated in the Basic System Diagram refer to Figure 1 1 This diagram is applicable to both hoist and travel operations F...

Страница 15: ...his diagram is applicable to both hoist and travel motions Figure 1 2 THYROMAT Components 1 Control box 2 Control panel 3 Keypad 4 Display 5 Snubber card 6 Phase shifter card 7 Relay card 8 Control ca...

Страница 16: ...x 180 x 202 6 kg THYROMAT BD 30 30 A M100 237 x 180 x 202 6 kg THYROMAT BD 60 60 A M100 237 x 180 x 202 6 kg THYROMAT BD 100 100 A M150 296 x 180 x 225 10 kg THYROMAT BD 150 150 A M150 296 x 180 x 22...

Страница 17: ...s BD Digital applications H Hoist applications T Travel applications 025 A 200 A 1 000 A 030 A 350 A 1 200 A 060 A 400 A 1 500 A 100 A 500 A 2 000 A 150 A 700 A 2 500 A 380 volts 415 volts 525 volts A...

Страница 18: ...he mechanical power that will be generated by the motor using the speed load and efficiency of the motion Step 2 If this data is not available use the electrical power for the specific duty Step 3 Obt...

Страница 19: ...C Altitude above sea level 1 500 meters The typical severe duty applications are as for BS 466 1984 cranes with a group mechanism in M5 to M8 heavy duty workshop warehouse and general hook service Th...

Страница 20: ...363 A 333 A M1000 500 A 416 A 357 A 454 A 416 A 700 A 583 A 500 A 636 A 583 A 1000 A 833 A 714 A 909 A 833 A M2000 1200 A 1 000 A 857 A 1 090 A 1 000 A 1500 A 1 250 A 1 071 A 1 363 A 1 250 A 2000 A 1...

Страница 21: ...CARDS INTO THE MOTHERBOARD NOT TO BEND THE CONNECTING PINS 2 DO NOT TOUCH ANY OF THE COMPONENTS ON THE CIRCUIT BOARDS THEY ARE VOLTAGE SENSITIVE AND MAY BE DAMAGED DESTROYED The control box contains...

Страница 22: ...not sensitive to incoming mains disturbances The thyristor trigger module incorporates a unique dynamic time amplitude transient clipping circuit 2 5 5 Snubber Card This card protects the thyristors...

Страница 23: ...st Supply variations 10 15 Digital inputs Control voltage Generated by the THYROMAT internal regulated supply circuit 10 V DC max 5 mA per input Outputs Main board 110 V or 220 Vac supply 5 x Relay ou...

Страница 24: ...edback Loss of torque detection Control method Phase angle control 3 phase 6 thyristors connected in line with motor stator in anti parallel configuration Operating frequency 50 Hz 1 Braking torque Va...

Страница 25: ...with filters recommended M500 400 A 1 830 W 1400 1800 400 M1000 500 A 2 280 W 1800 1400 500 Forced ventilation with filter recommended or open chassis plate installed inside crane girders where possib...

Страница 26: ...s data tables Step 4 Calculate new R 1 A R 1 A RA x Pm Pe Step 5 Calculate the motors rotor resistance K100 that will give 100 rated torque at start Obtain the motors open circuit rotor voltage RV fro...

Страница 27: ...eaker for the THYROMAT must be able to protect the THYROMAT unit against most current surges It is strongly recommended that a circuit breaker type such as manufactured by Merlin Gerin part number NS...

Страница 28: ...NS 400_ STR 23SE 400A M500 400 A NS 400_ STR 23SE 400A M1000 500 A NS 400_ STR 23SE 400A NS 630_ STR 23SE 630A 700 A NS 630_ STR 23SE 630A 1000 A NS800_ Micrologic 2 0 M2000 1200 A NS1000_ Micrologic...

Страница 29: ...between the relay outputs of the THYROMAT and the stator rotor contactors Contactors can be used as single units or where necessary may be used in parallel The rating of the continuous supply current...

Страница 30: ...used on festoon systems The selection of cable selection also largely depends on the environmental conditions that the crane will operate in 2 12 2 Control Supply Cables The THYROMAT uses interposing...

Страница 31: ...nt flowing in the circuit at the instant that the contactor is required to drop out This process increases the electrical life of the contactor and allows the use of contactors with AC1 ratings as opp...

Страница 32: ...e adjusted accordingly There are four basic configurations used to connect the rotor contactors the most popular configurations used are Delta and Star configurations and although not as popular V and...

Страница 33: ...on This method of protection does not monitor the thermal state of the motor accurately because it can only monitor the current drawn by the motor but does not take in consideration ambient and other...

Страница 34: ...lure to do so will render the warranty of the product null and void NOTE Although the larger higher current ratings THYROMAT units are compatible to lower currents the mounting holes will differ MH Au...

Страница 35: ...0 1 30 7 Hoist plugging Enable Hoist plugging Yes or No No 8 Hoist plugging V Hoist plugging voltage 20 to 80 5 50 9 Lower plugging V Lower plugging voltage 50 to 100 5 80 10 Brake release I Brake rel...

Страница 36: ...N A CONSERVATIVE MANNER AND ONLY WITH A FULL UNDERSTANDING OF EACH FUNCTION 3 2 1 CT Ratio NO PARAMETER DESCRIPTION SCALE INCREMENT DEFAULT 1 CT Ratio CT ratio 50 1 to 3000 1 50 1 This parameter selec...

Страница 37: ...PLATE VALUE FOR THE APPLICABLE DUTY Note This value should be determined during the design phase This value is to be used by the thermal model to calculate overload conditions 3 2 3 Overload Class NO...

Страница 38: ...ent to decelerate the load quickly due to the high inertia stored in the cable drum With Hoist Plugging enabled the control system will detect during upwards movement if natural retardation does not o...

Страница 39: ...80 5 50 This parameter is only active if parameter 7 Hoist plugging Yes active Hoists with high inertia require assistance during retardation by applying braking torque The percentage of Hoist pluggin...

Страница 40: ...is parameter sets the minimum stator current required to allow the brakes to be released As a general rule this current value must be equal or greater than the motor magnetizing current If this curren...

Страница 41: ...time out time compares the actual motor Lowering retardation profile against the profile set by this parameter In the event that the actual retardation is going to take longer than the set retardatio...

Страница 42: ...his case the parameter 15 setting is derived from the maximum contactor drop out time minus the close in time as in the example below Example Reversing contactors LC1 F265 Contactor drop out time with...

Страница 43: ...e the maximum close in time In this case the recommended phase shifter off delay time is based on the maximum close in time of the contactor plus parameter 15 s set value i e Maximum close in time par...

Страница 44: ...ith these parameters and the parameters need to be set to No When set as No This is the way that THYROMAT analogue and early digital units use to select the direction or rotation of the motor For Hois...

Страница 45: ...parameter returns all the parameters to factory default settings CAUTION IF IT IS NECESSARY TO CHANGE ANY PARAMETERS IT IS RECOMMENDED THAT THIS BE DONE IN A CONSERVATIVE MANNER AND ONLY WITH A FULL...

Страница 46: ...tage 0 to 90 5 40 10 Neutral PlugginV Neutral plugging Voltage 0 to 90 5 70 11 Neutral Decel P Neutral Deceleration Profile 2 to 20 sec 1sec 5 sec 12 Brake Plugging V Voltage to apply when plugging in...

Страница 47: ...0 1 to 3000 1 50 1 This parameter selects a current transformer ratio CT ratio Only CT ratios from the list can be used The available CT ratios are THE AVAILABLE CT RATIO S ARE 50 1 100 1 200 1 300 1...

Страница 48: ...OR THE APPLICABLE DUTY Note This value should be determined during the design phase This value is to be used by the thermal model to calculate overload conditions 3 4 4 Overload Class NO PARAMETER DES...

Страница 49: ...EMENT DEFAULT 8 Notch Plugging Notch plugging Yes or No Yes This parameter enables or disables plugging between Notches Refer to Parameter 9 below for further details 3 4 9 Notch Plugging Voltage NO P...

Страница 50: ...l deceleration is restricted by Parameter 10 above In the event that a quick deceleration is required the maximum Neutral plugging voltage Parameter 10 above may have to be raised to enable the motor...

Страница 51: ...on i e Motor is stalled Usually a setting of 70 is sufficient to enable the motion to operate satisfactory It is sometimes necessary to increase this voltage usually in the case of bad Travelling rail...

Страница 52: ...RIPTION SCALE INCREMENT DEFAULT 17 N4 Accel Acceleration rate for full speed acceleration 2 to 20 sec 1 5 Notch 4 acceleration profile is based on ramping the motor stator voltage as opposed to Notche...

Страница 53: ...jump from slow speed operation Speed ramp to full speed operation voltage Torque ramp 3 2 20 Separate Directional Signals NO PARAMETER DESCRIPTION SCALE INCREMENT DEFAULT 20 Sep dir signals Separate d...

Страница 54: ...ing to approximately 85 of its preselected value when the motor speed drops below a certain point The speed at which the Reduced Counter torque is applied is determined by this parameter 3 4 22 Notche...

Страница 55: ...applied gently i e The Brake plugging voltage ramps using a slope of 800ms from 0 to 100 voltage When the parameter is turned to No the Brake plugging is standard and will use a ramp slope of 200ms i...

Страница 56: ...Plug Plugging Voltage applied when N1 is selected in the opposite direction 30 to 100 1 50 10 Notch 2 Plug Plugging Voltage applied when N2 is selected in the opposite direction 30 to 100 1 60 11 Not...

Страница 57: ...selects a current transformer ratio CT ratio Only CT ratios from the list can be used The available CT ratios are THE AVAILABLE CT RATIO S ARE 50 1 100 1 200 1 300 1 400 1 500 1 600 1 800 1 1000 1 120...

Страница 58: ...R THE APPLICABLE DUTY Note This value should be determined during the design phase This value is to be used by the thermal model to calculate overload conditions 3 6 4 Overload Class NO PARAMETER DESC...

Страница 59: ...PEEDS IN EXCESS OF 30 ARE SELECTED SPECIAL ROTOR RESISTANCE DESIGN MAY BE NECESSARY CONSULT YOUR LOCAL MH AUTOMATION REPRESENTATIVE FOR ASSISTANCE 3 6 9 Notch 1 Plug 3 6 10 Notch 2 Plug 3 6 11 Notch 3...

Страница 60: ...RANE CONTROLLER MECHANICAL INSTALLATION 4 2 1 General The THYROMAT is a simple item to mount THYROMAT is provided with the correct fasteners to secure the unit on to the mounting surface In the event...

Страница 61: ...low for sufficient air circulation to aid in the cooling of the THYROMAT A minimum space of 150 mm at the top and 150 mm at the bottom of the THYROMAT must be free of obstructions to allow for suffici...

Страница 62: ...4 2 4 Mounting Arrangements Table 4 2 lists the mechanical mounting arrangement for the various THYROMAT controllers Table 4 2 Mechanical Mounting Arrangements of THYROMAT BD Digital Crane Controllers...

Страница 63: ...U Us se er r M Ma an nu ua al l Revision 8 6 SECTION 4 INSTALLATION 57 MECHANICAL SIZE MOUNTING HOLE ARRANGEMENT measurement in mm M350 200 300A Thyromat M500 400A Thyromat M1000 500 1000A Thyromat...

Страница 64: ...the mounting holes Using the electric drill and applicable drill bit drill the mounting holes take care not to damage any objects and or equipment that may be mounted on the opposite side of the mount...

Страница 65: ...eral WARNINGS 1 DO NOT ATTEMPT TO MAKE ANY CONNECTIONS TO THE THYROMAT WHILE IT IS CONNECTED TO THE MAINS POWER LIVE 2 AFTER DISCONNECTING THE THYROMAT FROM THE MAINS POWER USE A MULTI METER TO MAKE S...

Страница 66: ...nly a competent licensed Electrician or a suitably qualified person should be allowed to install the THYROMAT 2 It is important to shield the control electronics from any magnetic inductance that coul...

Страница 67: ...to the THYROMAT and thyristor stack make sure that the correct connector lug sizes are used refer to Table 4 4 Connector Lug Data Where fasteners are used to connect the electrical lugs to the THYROMA...

Страница 68: ...35 x 8 200 A 350 A 70 x 8 95 x 10 400 A 120 x 12 500 A 700 A 1 000 A 150 x 12 240 x 12 or 120 x 12 2 cable PH 150 x 12 2 cable PH 1 200 A 1 500 A 2 000 A 240 x 14 300 x 14 or 150 x 14 2 cable PH 240...

Страница 69: ...350 M500 M1000 M2000 TORQUE VALUES IN Nm 25 A 30 A 60 A N A 100 A 150 A N A 200 A 350 A N A 5 400 A 7 500 A 700 A 1 000 A 7 7 7 1 200 A 1 500 A 2 000 A 15 15 15 CURRENT DENSITY IN AMPERES PER mm2 25 A...

Страница 70: ...Controller Mechanical Size M100 M150 M350 M500 M1000 M2000 Multimeter X X X X X X Insulation tester X X X X X X Diagonal pliers X X X X X X Wire stripper or knife X X X X X X Lug crimping pliers X X...

Страница 71: ...ED STEP NOT USED 1 2 3 4 5 6 7 8 9 Figure 4 3 Digital Inputs for the Main Board Hoist Applications K01 Hoisting command and first speed step selection K02 Lowering command and first speed step selecti...

Страница 72: ...travel applications K12 Not used in standard hoist and travel spplications 4 4 3 Relay Outputs Connectors on the Main Board Figure 4 5 illustrates the installation diagram for the relay outputs from...

Страница 73: ...n special applications 4 4 4 Triac Outputs Control Panel Board Figure 4 6 illustrates the installation diagram for the triac outputs from the control board TRIAC RATINGS 600V AC 2A MAX 100 Ma CONTINUO...

Страница 74: ...N 68 4 4 5 Motor Current Inputs Figure 4 7 illustrates the installation diagram for the motor current inputs Figure 4 7 Motor Current Inputs Hoist Applications CTs always required Travel Applications...

Страница 75: ...RATION WARNINGS 1 HIGH VOLTAGE COMPONENTS ACCIDENTAL CONTACT WITH THYRISTOR STACKS CAN RESULT IN FATAL INJURIES 2 ONCE CONNECTED TO THE MAINS SUPPLY ALL INTERNAL COMPONENTS OF THE CONTROL UNIT EXCEPT...

Страница 76: ...e rotor resistances are wired correctly MH Automation always provides the correct values of the resistance steps on the respective rotor schematic diagram Follow these correctly to ensure that motor p...

Страница 77: ...ge The Incoming 3 phase supply has a phase imbalance Step 8 Input the motor parameters as necessary At this stage the only parameter which should be modified are the parameters which refer to the moto...

Страница 78: ...sary to replace it with a standby spare motor Under a great discrepancy on the rotor voltage the rotor resistance which was calculated around the motor name plate values is going to be inadequate too...

Страница 79: ...reconnected as recommended and proceed with the next step Step 12 No load test Run the motion in both directions notch by notch to ensure that the direction of rotation is correct and there are no oth...

Страница 80: ...peed and then returned to neutral position the deceleration to full stop should be achieved within reasonable time i e approximately 3 sec At stop the brakes should apply when the motor is at standsti...

Страница 81: ...t contactor remains activated providing the motor the opportunity to apply counter torque in order to maintain the lowering speed In a no load condition the lower contactor may be energized to operate...

Страница 82: ...vided before the brake is released Selection of one of the three slow speeds will regulate the motor to the associated speed in the event that full speed is selected the motor will accelerate smoothly...

Страница 83: ...ete panel The display has back lighting to aid the identification of the displayed data under darkened conditions The back lighting can only be activated in the main menu page after the power up cycle...

Страница 84: ...d capacity 3RD Status 4TH Drive healthy drive status Second display page MOTOR 3 PHASE CURRENTS MONITORING PAGE 1ST Joystick position and speed This page displays the current transformer inputs take n...

Страница 85: ...the each of the faults occurred 6 3 KEY PAD PUSH BUTTONS The keypad of the THYROMAT BD Digital Crane Controller has eight push buttons Table 6 2 lists the push buttons and their functions Table 6 2 K...

Страница 86: ...on 8 6 SECTION 6 OPERATION OF CONTROL PANEL 80 6 4 CONTROL PANEL OPERATION Navigating through the Display by using the Keypad is logical and structured as detailed in figure 6 3 Menu Navigation Chart...

Страница 87: ...ey to enter the parameters list 4 Scroll through the parameters with and keys 5 To modify a parameter scroll or v to the correct value then use the or keys to move to the next parameter 6 To save the...

Страница 88: ...illustrated in Figure 6 4 Figure 6 4 Set Time Page The SET TIME page displays the hour minute day month and year The cursor indicates the field which can be adjusted Table 6 4 lists the field name and...

Страница 89: ...ault history list A typical fault history menu page is illustrated in figure 6 5 Figure 6 5 Fault History Menu Page The fault history data is displayed in four rows The following details the displayed...

Страница 90: ...8 3 b Loss of phase 3 Yes Complete phase loss 0 Amps detected by current transformer input 3 6 8 3 c Current feedback Yes All 3 motor currents missing 6 8 4 Stack temp Yes 1 Excessive stack temperatur...

Страница 91: ...6 8 16 Power On Test Yes Routine CPU Test at power up of the unit failed 6 8 17 Brake Release Yes One of several of the conditions required before the brakes are released has failed 6 8 18 Error Code...

Страница 92: ...actual rotor speed rotation hence the increase in rotor frequency output i e motor slip 1 Possible causes Directional contactor failed to energize A rotor feedback may occur if the control supply is...

Страница 93: ...n ascertain if there is a relevant discrepancy in readings A fault such as this one may be caused by a faulty Thyristor or by a faulty trigger module built into the Phase Shifter card The quickest way...

Страница 94: ...8 3 c loss of phase 3 The loss of stator phase current occurred on C T input 3 Possible causes The possible causes of this fault are similar to the ones described under Current Unbalance Fault refer t...

Страница 95: ...Possible causes Crane has been overloaded Excessive long periods of slow speed operation Unusual mechanical friction caused by failure of mechanical components such as the brakes not releasing faulty...

Страница 96: ...tator or rotor causing a loss of torque on the motor Damaged stator or rotor cables Hoist loss of torque detection is disabled once the motor has achieved a speed 75 in 4 th notch This is required due...

Страница 97: ...circuit breaker crane main contactor and crane main isolator The phase rotation is incorrect or has been made incorrect during maintenance routine work on supply rails Mains supply dropped below 70 of...

Страница 98: ...oint failure of both signals This type of faulty condition has been split into 3 sub categories to facilitate fault finding The sub categories are 6 8 14 a RFB CURRT LOSS S This fault condition indica...

Страница 99: ...he minimum drive level to drop below 3 5V but not sufficiently low to cause a CPU brownout i e 2 7V a drive level fault will be logged This usually is reset as soon as the supply voltage returns to it...

Страница 100: ...further tests are performed which in the event of a failure they will be displaying their specific code These tests are watchdog test code 101 CPU brownout test code 102 CPU loss of messages code 103...

Страница 101: ...Error Code 102 This error code indicates a CPU brownout reset The CPU power supply dropped below 2 7V DC 6 8 22 Error Code 103 This error code indicates a CPU reset due to an over flow of software po...

Страница 102: ...aced will greatly reduce equipment down times A second option would be to keep a spare set of modules for the THYROMAT The identification and replacement of faulty cards require a suitably qualified p...

Страница 103: ...to BDT 2000 2 OA 0020 2 Phase shifter card All BD 3 25 2 to BD 3 2000 2 OA 1070 4 Relay control card All BD 3 25 2 to BD 3 2000 2 OA 0022 Snubber card All BD 3 25 2 to BD 3 2000 2 AO 14901 Mother boar...

Страница 104: ...will in all cases be suitable as spares but installed thyristors may not necessary be the same Fans M150 fan 4 Compact fan M150 BD 3 100 to BD 3 150 M450 fan 4 Compact fan M350 BD 3 200 to BD 3 350 M...

Страница 105: ...hyristor Phase Arm 400A 525V 525500 ARM Thyristor Phase Arm 500A 525V 525700 ARM Thyristor Phase Arm 700A 525V 5251000 ARM Thyristor Phase Arm 1000A 525V 5251200 ARM Thyristor Phase Arm 1200A 525V 525...

Страница 106: ...l Place the complete wrapped unit into a strong cardboard box or suitable container The unit is ready for shipping Components It is advised that the following procedure should be followed when packagi...

Страница 107: ...Delay EEPROM Electrically Erasable Programmable Read Only Memory flc Full Load Current G Gravitational Force Hz Hertz Cycles per Second I Current Ith Thermal Current K Coefficient value of rotor resis...

Страница 108: ......

Отзывы: