Device control
Page 37
PROFIBUS-Manual Servo positioning controller DIS-2 48/10 FB
Version 2.0
In reception telegrams 0..2, control word 1 is bound to a fixed position. The system evaluates the
control word always as the last datum. This means that new target positions are written first. A
command to start a positioning run, which is transmitted simultaneously, therefore always refers to the
data transmitted in the same telegram.
Some bits have different meanings depending on the operating mode. The two following tables show
the meanings for the two operating modes.
Bit
Meaning
Behaviour
0
ON / OFF (OFF 1)
See the “Device control” section,
chapter 9.4
State diagram and device control
1
No coast stop (no OFF 2) /
coast stop (OFF 2)
2
No quick stop (no OFF 3) /
quick stop (OFF 3)
3
Enable Operation / Disable Operation
4*
1: Enable ramp generator
0: Reset ramp generator
1: All speed setpoints enabled
0: All speed setpoints disabled
5*
1: Unfreeze ramp generator
0: Freeze ramp generator
1: Setpoint ramp enabled
0: Ramp stopped (frozen)
6*
1: Enable setpoint
0: Disable setpoint
1: All setpoint inputs for the ramp enabled
0: All setpoint inputs for the ramp deactivated
7
Fault acknowledge
(edge from 0->1)
Active errors are acknowledged if possible
8*
Jog 1 ON / Jog 1 OFF
The speed of motion of the “positive jogging”
position set is preset as a speed setpoint through
the ramp
9*
Jog 2 ON / Jog 2 OFF
The speed of motion of the “negative jogging”
position set is preset as a speed setpoint through
the ramp
10
1: Control by PLC
0: No control by PLC
1: Control word evaluated
0: Control word not evaluated
11*
Device-specific
free
12-15
Device-specific
free
*: Different meaning in another operating mode.
Table 9.1: Control word 1 for speed control mode