![Metronix DIS-2 48/10 FB FS STO Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/metronix/dis-2-48-10-fb-fs-sto/dis-2-48-10-fb-fs-sto_manual_1780032031.webp)
Physical units
Page 31
PROFIBUS-Manual Servo positioning controller DIS-2 48/10 FB
Version 2.0
7
Physical units
For trouble-free operation, the units of the process data transmitted on the field bus have to be defined.
They can be set in the menu
Physical units Profibus
called by
Parameters/Fieldbus/Profibus
.
The
parameters of the physical units should be set once and then remain unchanged during a
running application.
Unit-related factors are calculated internally so that all the user has to do is to select the desired unit.
The gear ratio and the feed constant are stated as separate parameters.
Figure 7.1 shows the physical unit set-up menu of the DIS-2 ServoCommander
TM
program.
Figure 7.1:
Setting of physical units
When the physical units are entered, the firmware automatically calculates conversion factors. They
consist of a numerator and a denominator which can comprise a maximum of 32 bits each. If an
overflow occurs when the factors are entered, the value will be rejected. In this case, the factors or the
physical units have to be corrected.
It has to be taken into consideration that some quantities cannot always be used in a sensible manner.
A purely rotative system, for example, does not require a feed constant. Apart from this, the feed
constant has a physical unit. If this unit is not parameterized correctly, the feed constant will be
ignored.