Device control
PROFIBUS-Manual Servo positioning controller DIS-2 48/10 FB
Version 2.0
9
Device control
9.1
Overview
To make the control of a field device (slave) independent from the various manufacturers, two data
words have been specified in the PROFIdrive specification (4).
Control word 1
is used to control the
major device functions by the master whereas the status of the device is read back in s
tatus word 1
.
The PROFIdrive profile defines the order in which certain bits have to be set, e.g. to enable the power
stage of the servo controller.
Device control of servo positioning controllers DIS-2 48/10 FB follows the state diagram specified in the
PROFIdrive profile. The implementation and potential manufacturer-specific deviations are described
in detail in
chapter 9.4 State diagram and device control
The implementation of the control word and the status word only follows the PROFIdrive specification.
Deviations from the specifications are marked. In addition, some bits have different meanings
depending on the operating mode. In the following chapters, first the control word and then the status
word are described. Then the device control mechanism using these two data words is explained.
9.2
Control word 1
Control Word 1
is used to control various device functions, e.g. controller enabling. Some bits have
corresponding meanings. The use of these bits is described in
chapter 9.4 State diagram and device
. The meaning of the individual bits follows the PROFIdrive profile. In addition, some functions
are a manufacturer-specific and some bits have a manufacturer-specific functionality.
PNU
967
Subindex
0
Name
Control word 1
Data type
UINT16
Access
rw
Unit
-
Value range
-
Default value
0