FP4, FP4W
53
12.6.2 Totalizer archive
Organization of additional header in the totalizers archive file:
CHANNEL, DESCRIPTION, TOTALIZER 1 TYPE, TOTALIZER 1 UNIT, TOTALIZER 2
TYPE, TOTALIZER 2 UNIT
CHANNEL
– the channel number
DESCRIPTION
– channel description, depending on the settings in the device
TOTALIZER 1 TYPE/
TOTALIZER 2 TYPE
– totalizer operation mode: ‘ ’ – disabled; ‘1’ – unresettable;
‘2’ – resettable; ‘3’ – daily; ‘4’ – weekly; ‘5’ – monthly
TOTALIZER 1 UNIT/
TOTALIZER 2 UNIT
– unit assigned to the totalizer
Organization of records in the totalizers archive file:
DATE, TIME, DST, CHANNEL1: TOTALIZER1, CHANNEL1: TIMER1, CHANNEL1:
TOTALIZER2,
CHANNEL1: TIMER2, … , CHANNEL6: TIMER2, CRC2
DATE
– date of the record in YY-MM-DD format
TIME
– time of the record in HH:MM:SS format
DST
– information about summer (1) or winter (0) time enabled
CHANNEL X:
TOTALIZER Y
– value of totalizer (X – channel number from 1 to 6; Y – totalizer
number: 1 or 2)
CHANNEL X:
TIMER Y
– the value of the timer which counts the operation time of totalizer
1 or 2, the value is in seconds (X
– channel number from 1 to 6;
Y
– timer number: 1 or 2)
CRC2
– CRC control
12.6.3 Event archive
Organization of records in the events archive file:
DATE, TIME, DST, EVENT CODE, CRC2
DATE
– date of the record in YY-MM-DD format
TIME
– time of the record in HH:MM:SS format
DST
– information about summer (1) or winter (0) time enabled
EVENT CODE
– event code (more information below)
CRC2
– CRC control
The event archive records the following events:
SYS:STOP
– Power supply switched off
SYS:START
– Power supply switched on
ARCH:NEW
– Created a new archive file
ARCH:STOP
– Stopped archivization of data/totalizers
ARCH:START
– Started archivization of data/totalizers
SYS:NEW SETTINGS
– New settings saved
SYS:TIME CHANGED
– Changed time