FP4, FP4W
16
Fig. 5.4 Layout of jumpers inside the FP4W device.
5.1.1 Configuration of jumpers related to analogue inputs (IN1, IN2)
INPUT 1 (IN1)
INPUT 2 (IN2)
Input type:
J11 J12 J13 J14 J15 J16 J17 J21 J22 J23 J24 J25 J26 J27
0/4-20mA
X
X
X
X
X
X
R/RTD
X
X
X
X
X
X
U (
±10V)
X
X
X
X
Notes:
The
‘X’ sign means closed jumper. The device is delivered in the 0/4-20mA
configuration. Each input can be independently configured to a different operating mode.
5.1.2 Configuration of jumpers related to PULS type inputs (IN3, IN4)
INPUT 3 (IN3)
INPUT 4 (IN4)
Input to connect:
J31 J32 J33 J34 J41 J42 J43 J44
OC or passive contact type transmitter
X
X
EH type current transmitter
X
X
NAMUR type current transmitter
X
X
active voltage transmitter
Notes:
The ‘X’ sign means closed jumper. The device is delivered is the OC/contact
configuration (the additional filtering capacitor disconnected). To connect the additional
filtering capacitor, configure jumpers according to the table below. Each input can be
independently configured to a different operating mode.
INPUT 3 (IN3)
INPUT 4 (IN4)
J31 J32 J33 J34 J41 J42 J43 J44
FILTER ON
X
X