48
If the signal on the selected relay contact of X6 is not
broken, this will be regarded as a negative test. The
door can now only close “hold to run”.
Check the connections of the light curtain and the light
curtain itself. Please refer to the user manual of the
implemented light curtain in order to diagnose the light
curtain itself.
F 5.0
Software error.
Controller restart by software. Switch off power to
controller and switch on power once again. Change the
control circuit board if this message keeps returning.
F 5.1
Error in ROM memory.
ROM memory check failed. Restart the controller.
Change the control circuit board if this message keeps
returning.
F 5.2
Error in CPU.
CPU register test error. Switch off power to controller
and switch on power once again. Change the control
circuit board if this message keeps returning.
F5.3
Error in RAM.
RAM test error. Switch off power to controller and
switch on power once again. Change the control circuit
board if this message keeps returning.
F 5.4
Internal control error.
Plausibility error. Switch off power to controller and
switch on power once again. Change the control circuit
board if this message keeps returning.
F 5.5
DES (digital end switch) error.
Cannot communicate with Digital end switch. Check the
connections of the digital end switch on X22. Swap the
digital end switch of the drive unit if this is faulty.
F 5.6
Error in door movement.
Check the door mechanism.
Check the phases to the drive unit (U-V-W)
Check the rotation movement digital end switch.
Door movement only still possible with internal push
buttons.
Note!! Door end positions may not be secure!
F 5.7
Error in direction of rotation.
The direction of rotation has changed since
programming the end positions. Check if the door opens
with the up button; if this is the case, use parameter 9.5
in the menu to restore the controller to factory settings.
And re-program the end positions.
If the drive unit runs in the wrong direction, swap the U
and W connections in order to change the direction of
rotation of the drive unit.
F 5.9
Duration control.
Maximum duration exceeded. Check the door
mechanism. Check if the time that has been configured
for parameter 2.1 if sufficient and configure again if
necessary.
F 7.0
No mains power present.
This message is shown if mains power is not present.
The controller will then only operate on the batteries.
The door can no longer be operated. This will only start
closing if the fire or smoke detector contact is activated
or if a decision has been made to lower the door if the
battery voltage is low. The door will also close if the
batteries are completely empty.
PLEASE NOTE: in this
case, the safety features and end switches will not
work.
F 7.1
Low battery voltage.
This message is shown if there is not enough voltage in
the batteries. Make sure that mains power is present. If
this is present, check if the batteries are being charged.
If the message persists, replace the batteries and/or the
power/charger.