If the safety edge or photocell safety feature is activated in case of closure during a fire alarm,
power failure or almost empty battery, the controller will regard the concerned safety feature to
be faulty if it is activated continuously for 120 seconds (factory setting) or longer, and the door
will then continue closing without the safety feature!
-
It is possible to connect an escape button, whereby the door can be opened in case of a fire
alarm (if mains power is still present), to allow someone to escape. The door will close again
after a configured time. There is also a setting that allows the door to be opened again with
the open button if mains power is available. The door will close again when the button is
released.
-
Parameter 8.5 in the menu can be used to activate a maintenance cycle. The LED will flash
red and green alternately if this has been activated and the number of configured cycles has
been reached. A message will appear on the display. Parameter 8.7 can also be used to close
the door once the number of configured movements has been reached.