40
Parameter Description
Settings
photocell position and ignore the photocell during closing
from that point.
8.7
Parameter series 3, emergency settings
Parameter Description
Settings
3.1
Choice end position door
bottom during
alarm/emergency in
combination with NES
.1) Use normally closed end switch; deactivate end
switch S6.
X
.2) Use end switch (S6) as “Over-close”.
.3) Use normally closed end switch and use (S6) as ES
open (intermediate position) in case of fire.
3.2
Autom. close time when
using escape button during
fire.
1 to 240 seconds.
1 sec.
3.3
Function “open” button
during fire
.1) Deactivated.
X
.2) Hold to run open and close.
3.4
Extend FD function after
FDC has been active.
0 to 240 seconds.
0 sec
.
3.5
Number of closure
attempts if safety
edge/photocell operated
during emergency.
0 to 10
The total will be indefinite if this parameter is set to 0.
0
3.6
Action if safety edge
and/or photocell are not
detected when the FDC,
SDC or door close become
active, in case of low
battery voltage or loss of
power.
.1) Ignore: door will close without Safety feature.
Once safety edge is activated, the door will continue
to close without safety feature after ≥120 sec.
X
.2) Do not ignore: door will remain open for max. 120
sec. If the safety feature is still activated, the door will
close without the safety feature.
.3) Do not ignore: door will remain open.
3.7
Function during mains
power failure
.1) Immediately close door.
.2) Close door if battery power is too low.
X
.3) Only issue Warning. (door will close if batteries do
not have enough capacity to keep door open).
3.8
Function Escape button
.1) Always active.
X
.2) Only active for Fire alarm input 2.
.3) Only active for Fire alarm input 1.
.4) Inactive.