27
7.5
Configuring end switches DES
Once the end position has been set, the status of the door will be shown on the display using the
symbols below.
Move open
End position Move close End position Random Pre-end Both limit
Open
Close Position Position switches
activated
Figure 7 status symbols
7.6
Configure “over-close DES position”
The “Over-close” position is set (as standard) at the same position as the saved ‘end position closed’.
Use parameter 1.7 to configure this position at the position where the door must stop in case of fire
alarm, smoke alarm, loss of power or almost empty battery, if the option has been selected (in the
menu) to lower the door until this position.
Start programming: Check direction of rotation
Change direction of rotation, if necessary
Move to OPEN final limit position
Save OPEN final limit position
Move to CLOSED final limit position
Save CLOSED final limit position