Form 44201460
17
Mar 2019
HEATER MOUNTING ANGLE
12.1)
Every heater is supplied with an angle gauge. The gauge is attached with tape to the heater control side.
The angle gauge is used in combination with a level to ensure that the heater is installed at one of the mounting
angles of 0
0
, 15
0
, 30
0
, 45
0
and 60
0
.
Hold the side of the angle gauge without label flush against the glass surface. Hold a level against the other side of
the angle gauge and find the desired installation angle of the heater. Verify that the level is vertical, adjust heater
angle if needed.
Note: If a heat shield is installed its location must match the heaters angle (see Section 21.0).
This process must be repeated for both ends of the heater.
INDOOR INSTALLATION – HANGING METHODS
12.2)
When the heater is used for an Indoor Installation then the following hanging methods may be used.
The heater can be hung from the ceiling, secondary steel work, etc. using chains, threaded rods and other approved
hanging materials. All hanging materials must have a minimum working load of 115 lbs. Any “S” hooks must be
crimped closed after installation.
Note:
When hanging the heater hanging materials which allow the heater to move the gas connection must be
established using an approved flexible gas hose of a minimum of 24” length.