SAFETY 

1.0)

This  heater  is  a  self-contained  infrared  radiant  ceramic  heater.  Safety  information  required  during  installation  and 
operation  of  this  heater  is  provided  in  this  manual  and  the  labels  on  the  product.  The  installation,  service  and 
maintenance of this heater must be performed by a contractor qualified in the installation  and service of gas fired 
heating equipment. 
All  personnel  in  contact  with  the  heater  must  read  and  understand  all  safety  information,  instructions  and  labels 
before operation. The following symbols will be used in this manual to indicate important safety information. 

 

Warning instructions must be followed to prevent or avoid hazards which 
may cause serious injury, property damage or death. 

 

 

 

Caution  instructions  must  be  followed  to  prevent  incorrect  operation  or 
installation  of  the  heater  which  may  cause  minor  injury  or  property 
damage. 
 

 

INSTALLER RESPONSIBILITY 

2.0)

The installer is responsible for the following: 

 

The  heater  installation,  electrical  and  gas  supplies  must  be  installed  in  accordance  with  these  installation 
instructions and any applicable codes and regulations. 

 

Every heater shall be located with respect to building construction and other equipment so as to permit access to 
the heater.  

 

Each installer must follow the clearances to combustible materials for the heaters. 

 

It  is  important  to  read  and  understand  section  4.0)  where  outdoor  spaces  are  defined  any  space  other  than 
outdoors is an indoor installation.  

 

Install the heater so  that the supports and hangers are correctly spaced in  accordance with  these instructions. 
The heater must be supported by materials having a working load limit of at least 115 lbs. 

 

To  install  the  heater  in  an  adequate  free  area  to  allow  the  products  of  combustion  to  freely  escape  from  the 
heater. The heater must not be installed in recessed spaces or enclosure and alcoves. 

 

Supply the owner with a copy of these Installation and Operation Instructions. 

 

If the heater is installed indoors, ventilation by gravity or mechanical means shall be provided to supply at least 4 
CFM of exhaust air per 1,000 Btu/hr of operating heat input. 

 

Never use the heater as a support for a ladder or other access equipment. Do not hang anything from the heater. 

 

Supply all installation materials necessary that are not included with the heater. 

 

Check the nameplate to make sure that the burner is correct for the gas type in the building. 

 

Use  the  provided  angle  gauge  (see  Section  12.1)  to  ensure  the  heater  is  installed  at  the  approved  installation 
angles of 0

0

, 15

0

, 30

0

, 45

0

 and 60

0

 degrees with the heat shield installed.  

 

 

GENERAL INFORMATION 

3.0)

This heater is a self-contained infrared radiant ceramic patio heater for use in locations where flammable gases or 
vapors are not generally present and is intended for space heating non-residential spaces.  

 

This patio heater model is approved to two different heater standards: 

 

A “Patio Heater” for Outdoor Use in Residential and Commercial/Industrial Applications. 

 

And as a “Gas-Fired High Intensity Infrared Heater” for Indoor Spaces of Commercial/ Industrial Applications. 
Not for use in residential dwellings. 

Note: 

A residential dwelling is a domicile intended for use by one or more persons and that 

includes one or more areas, such as those used for cooking, eating, living, sleeping, or a sanitary 
facility. A residential dwelling does not include a workshop, or outdoors.  

 
 

Содержание 44625000

Страница 1: ...and understood before installing operating or servicing this heater Make certain to follow the Clearances to Combustibles Section 4 This heater is intended for use with either Natural Gas or Propane G...

Страница 2: ...L CONNECTION WIRING DIAGRAM 29 16 1 FIELD CONNECTIONS AND WIRING DIAGRAMS 2 STAGE 29 16 2 FIELD CONNECTIONS AND WIRING DIAGRAMS SINGLE STAGE 24V 31 16 3 FIELD CONNECTIONS AND WIRING DIAGRAMS SINGLE ST...

Страница 3: ...heater must be supported by materials having a working load limit of at least 115 lbs To install the heater in an adequate free area to allow the products of combustion to freely escape from the heat...

Страница 4: ...he control compartment air passageways and burner of the heater be kept clean If any changes are made to the patio or building structure after the heaters are installed such as adding plastic curtains...

Страница 5: ...ust be installed in accordance with ANSI NFPA 409 latest edition Standard for Aircraft Hangars ANSI NFPA 88a latest edition Standard for Parking Structures and ANSI NFPA 88b latest edition Standard fo...

Страница 6: ...ustibles are defined as a surface temperature of 117 F above ambient temperature OUTDOOR Spaces are defined as a shelter no more inclusive than a with walls on all sides but with no overhead cover b w...

Страница 7: ...the sign is posted in a location where it is easily accessed Clearances to combustibles are posted on the heater In areas used for storage of combustible materials where they may be stacked below the...

Страница 8: ...siding canvas tri ply etc may be subject to degradation at lower temperatures It is the installer s responsibility to assure that adjacent materials are protected from degradation See below the possib...

Страница 9: ...siding canvas tri ply etc may be subject to degradation at lower temperatures It is the installer s responsibility to assure that adjacent materials are protected from degradation See below the possi...

Страница 10: ...Electrical Supply Current Rating Weight Natural or Propane NPT Male 120 Volt 60Hz 1 Phase 0 1 Amp 55 lbs Module Electrical Rating Ignition System direct spark Input Control 18 30 VAC 50 60 Hz class 2...

Страница 11: ...60 degree Radiant output reduction 3 13 29 50 5 It is recommended to place the heaters in the area of greatest heat loss facing into the patio area The table below shows minimum area coverage per heat...

Страница 12: ...stance D for angled heaters applies when they are facing towards each other Note Local codes may have special requirements regarding head clearance requirements Some local codes require all portions o...

Страница 13: ...optional accessories available for the Wind Blocker Patio heater PN Description Picture 44560350 Wall Ceiling Telescopic Mounting Bracket Kit 15 22 overhead space check clearances to combustibles spac...

Страница 14: ...Mount Bracket Kit 10 fixed installation for minimum overhead clearance This bracket is only for horizontal mounting with the heat shield 44566300 Heat Shield Kit Reduced clearances to combustible opti...

Страница 15: ...Care must be taken when up packing the heater Carefully open the top of the heater as indicated on the labels at the side of the shipping box An angle gauge is attached to the heater s control side wi...

Страница 16: ...pan between supporting beams f The appliance should be located with respect to building construction and other equipment to permit access to the appliance for servicing etc f The heater must be instal...

Страница 17: ...er angle if needed Note If a heat shield is installed its location must match the heaters angle see Section 21 0 This process must be repeated for both ends of the heater INDOOR INSTALLATION HANGING M...

Страница 18: ...range of lengths and approved mounting angles of 150 300 450 and 600 44560350 KIT BRACKET WALL CEILING 15 22 CEILING FOR USE WITH HEAT SHIELD telescoping 44560351 KIT BRACKET CEILING 22 30 FOR USE WI...

Страница 19: ...angle and whether a heat shield is installed 15 22 Bracket With heat shield telescope hole positions 22 30 Bracket Without heat shield telescope hole positions Mounting Angle INDOOR OUTDOOR INDOOR OUT...

Страница 20: ...inimum working load of 115lbs 12 3 2 HEATER ATTACHMENT TO HANGING BRACKETS The heater can be attached to the hanging brackets in angles of 150 300 450 and 600 Choose the desired heater mounting angle...

Страница 21: ...UT 2 4 02352000 PHSMS 8 x 1 2 AB POINT SS BLK OXIDE 8 5 44568139 RAIL HEAT SHIELD HANGER PAINTED 1 6 44566189 HEAT SHIELD ROLLED PAINTED 1 7 44568149 HOLDER BRACKET PAINTED 2 8 43247112 LABEL INDOOR C...

Страница 22: ...eld hanger rail to the holder bracket using 2 black oxide 8 screws on each end Horizontal position shown below IMPORTANT Use the Acorn nuts at the control end of the heater as shown in the illustratio...

Страница 23: ...ERAMIC GLASS 14 0 Only install the ceramic glass once the heater has been attached to a suitable gas see Section 15 0 electrical supply see Section 16 0 and has been commissioned see Section 18 0 Read...

Страница 24: ...der the Glass Retainer at the heaters control enclosure side At this point the glass will be flush with the heater at the insertion point Note If the ceramic glass does not slide in easily review posi...

Страница 25: ...of the heater h The gas pipe flexible hose and connections must be self supporting The gas pipe work must not bear any of the weight of the heater or any other suspended assembly i This appliance is e...

Страница 26: ...UCTIONS FOR PRESSURE TEST GAUGE CONNECTION 15 1 INLET GAS PRESSURE CHECK 15 2 1 The installer will provide a 1 8 N P T tapped plug accessible for test gauge connection immediately upstream of the gas...

Страница 27: ...e solenoid Do not energize the HI solenoid 2 Remove regulator cover screw from the low outlet pressure regulator see Figure 1 below and turn screw clockwise to increase pressure or counterclockwise to...

Страница 28: ...r shall be connected to a permanently live electrical circuit one that is not controlled by a light switch 4 The power supply to the unit should be protected with a fused disconnect switch or circuit...

Страница 29: ...below shows the internal wiring diagram of the heater and the optional external connections depending on how the heater will be controlled FIELD CONNECTIONS AND WIRING DIAGRAMS 2 STAGE 24V 16 2 The f...

Страница 30: ...44201460 30 Mar 2019 A LOW VOLTAGE 24V 3 POSITION SWITCH CONNECTIONS SINGLE HEATERS B LOW VOLTAGE 24V 3 POSITION SWITCH CONNECTIONS MULTIPLE HEATERS C LOW VOLTAGE 24V THERMOSTAT CONNECTIONS SINGLE HEA...

Страница 31: ...The figure below shows the internal connection to operate the heater turning on and off 24V power to the heater with a permanent live power supply Important To operate the heater as single stage a jum...

Страница 32: ...GLE STAGE 120V 16 4 The figure below shows the internal connection to operate the heater turning on and off 120V power to the heater Important To operate the heater as single stage with 120V all three...

Страница 33: ...d and the minimum vent flow required is as follows WB35 N2and L2 140 cfm The General Ventilation Rules outlined in ASHRAE GUIDE AND DATA BOOK should be observed when locating vents Exhaust vents must...

Страница 34: ...occurs after successful ignition the appliance will attempt one re ignition before going to Lockout conditions 9 To shut down the appliance for short periods of time switch off the electrical supply t...

Страница 35: ...door Clearances to Combustibles Check that the area has not been closed in making it an indoor installation If any changes have been made then the clearances and ventilation requirements for Indoor in...

Страница 36: ...rt or debris including spider webs Foreign Objects Check and remove any foreign objects that are logged between the heat shield and the heater Ceramic Glass Clean the glass from the inside and outside...

Страница 37: ...Form 44201460 37 Mar 2019...

Страница 38: ...logo emblem s final position to be at the control side of the heater 4 2 Slide the glass into the Glass Retainer Rails The glass must be held parallel to the Glass Retainer Rails during assembly The...

Страница 39: ...Remove any foreign matter from the electrode tips and check that the spark gap is 199 5mm If the electrode flame sensor rods are badly oxidized replace the electrode flame sensor in the reverse order...

Страница 40: ...is removed from the illustration for clarity Loosen the panel nut 1 using a 19mm end wrench and remove from the gas valve manifold 2 Disconnect the wires to the gas valve 3 Remove the 4 screws from t...

Страница 41: ...e it from the heater 3 Disconnect the transformer lead wires Remove the screws 3 holding the transformer and remove it from the heater REMOVAL OF MAIN BURNER EMITTER ASSEMBLY 21 6 A Remove the ceramic...