Form 44201460
2
Mar 2019
SAFETY
1.0)
This heater is a self-contained infrared radiant ceramic heater. Safety information required during installation and
operation of this heater is provided in this manual and the labels on the product. The installation, service and
maintenance of this heater must be performed by a contractor qualified in the installation and service of gas fired
heating equipment.
All personnel in contact with the heater must read and understand all safety information, instructions and labels
before operation. The following symbols will be used in this manual to indicate important safety information.
Warning instructions must be followed to prevent or avoid hazards which
may cause serious injury, property damage or death.
Caution instructions must be followed to prevent incorrect operation or
installation of the heater which may cause minor injury or property
damage.
INSTALLER RESPONSIBILITY
2.0)
The installer is responsible for the following:
The heater installation, electrical and gas supplies must be installed in accordance with these installation
instructions and any applicable codes and regulations.
Every heater shall be located with respect to building construction and other equipment so as to permit access to
the heater.
Each installer must follow the clearances to combustible materials for the heaters.
It is important to read and understand section 4.0) where outdoor spaces are defined any space other than
outdoors is an indoor installation.
Install the heater so that the supports and hangers are correctly spaced in accordance with these instructions.
The heater must be supported by materials having a working load limit of at least 115 lbs.
To install the heater in an adequate free area to allow the products of combustion to freely escape from the
heater. The heater must not be installed in recessed spaces or enclosure and alcoves.
Supply the owner with a copy of these Installation and Operation Instructions.
If the heater is installed indoors, ventilation by gravity or mechanical means shall be provided to supply at least 4
CFM of exhaust air per 1,000 Btu/hr of operating heat input.
Never use the heater as a support for a ladder or other access equipment. Do not hang anything from the heater.
Supply all installation materials necessary that are not included with the heater.
Check the nameplate to make sure that the burner is correct for the gas type in the building.
Use the provided angle gauge (see Section 12.1) to ensure the heater is installed at the approved installation
angles of 0
0
, 15
0
, 30
0
, 45
0
and 60
0
degrees with the heat shield installed.
GENERAL INFORMATION
3.0)
This heater is a self-contained infrared radiant ceramic patio heater for use in locations where flammable gases or
vapors are not generally present and is intended for space heating non-residential spaces.
This patio heater model is approved to two different heater standards:
A “Patio Heater” for Outdoor Use in Residential and Commercial/Industrial Applications.
And as a “Gas-Fired High Intensity Infrared Heater” for Indoor Spaces of Commercial/ Industrial Applications.
Not for use in residential dwellings.
Note:
A residential dwelling is a domicile intended for use by one or more persons and that
includes one or more areas, such as those used for cooking, eating, living, sleeping, or a sanitary
facility. A residential dwelling does not include a workshop, or outdoors.