HEATER SIZING GUIDELINES 

7.0)

Radiant heaters work like the sun to emit radiant heat directly to the space to increase the comfort of the patio 
guests. Suitable applications include patios, porches, outdoor shopping areas and pathways. 
The amount of temperature increase in outdoor patio spaces will be dependent on the following factors: 
1.

 

The number of heaters in the space is important to provide good coverage of the area to be heated. 

2.

 

Take  care  not  to  mount  the  heaters  too  low  or  too  close  together  this  can  make  people  directly  below  the 
heaters uncomfortable. 

3.

 

It is recommended to use a suitable windbreak to reduce the effects of direct wind on the patio. If an area is 
going to be unprotected and is a breezy location then  heaters may need to  be located closer together. Wind 
breaks must be designed to allow fresh air for ventilation. 

4.

 

Angling the heaters greater than 30 degrees should be avoided unless the mounting height is low, when the 
heaters are angled more than 30 degrees the radiant intensity is lower and will reduce the amount of heat felt 
by the guests. 

 When  angle  mounting  the  heater  the  radiant  output  will  decrease  approximately  by 

following:  

Mounting Angle 

15 degree 

30 degree 

45 degree 

60 degree 

Radiant output reduction 

3% 

13% 

29% 

50% 

 

5.

 

It is recommended to place the heaters in the area of greatest heat loss facing into the patio area. 

 

The table below shows minimum area coverage per heater for outdoor patio heating based on a 5 to 10°F (2.8 to 
5.6°C) temperature rise. 
 

Mounting Angle 

Mounting Height 

Breezy Exposed 

Location 

Moderately 

Protected 

Well 

Protected 

Horizontal 

8ft. – 11ft.  

(2.5 – 3.0m) 

8 x 8 ft 

(2.5 x 2.5m) 

10 x 10 ft. 

(3.0 x 3.0m) 

12 x 12 ft. 

(3.7 x 3.7m) 

Up to 30 Degrees Angled 

7ft. – 9ft. 

(2.1 – 2.7m) 

8 x 8 ft 

(2.5 x 2.5m) 

9 x 9 ft. 

(2.7 x 2.7m) 

11 x 11 ft. 

(3.3 x 3.3m) 

30 to 60 Degrees Angled 

6ft. – 8ft. 

(1.8 – 2.5m) 

Not Recommended 

8 x 8 ft. 

(2.5 x 2.5m) 

 
Note: When sizing the number of heaters to warm the patio, the area coverage given above may not provide the 
stated temperature rise under all weather conditions and will be dependent on heater placement. Minimums are 
shown as a guideline for human comfort.  For more assistance with patio heater sizing and layout please contact 
your local Mestek, Inc. representative. 
 

 

TYPICAL HEATER LAYOUTS 

8.0)

The diagram below shows the recommended spacing layout between heaters. 
 

 

Dimension 

Horizontal 

15 to 30 degree angle 

Above 30 degree angle 

Min. 

Max. 

Min. 

Max. 

Min. 

Max. 

A. Mounting Height 

8ft (2.5m) 

11ft (3.4m)  7ft (2.1m) 

9ft (2.7m) 

6ft (1.8m) 

8ft (2.5m) 

B.  Distance  to  the  end  of 
the patio 

0ft (0m) 

6ft (1.8m) 

0ft (0m) 

6ft (1.8m) 

0ft (0m) 

6ft (1.8m) 

C. 

Distance 

between 

heaters. 

8ft (2.5m) 

12ft (3.7m)  7ft (2.1m) 

11ft (3.4m)  6ft (1.8m) 

10ft (3.0m) 

Содержание 44625000

Страница 1: ...and understood before installing operating or servicing this heater Make certain to follow the Clearances to Combustibles Section 4 This heater is intended for use with either Natural Gas or Propane G...

Страница 2: ...L CONNECTION WIRING DIAGRAM 29 16 1 FIELD CONNECTIONS AND WIRING DIAGRAMS 2 STAGE 29 16 2 FIELD CONNECTIONS AND WIRING DIAGRAMS SINGLE STAGE 24V 31 16 3 FIELD CONNECTIONS AND WIRING DIAGRAMS SINGLE ST...

Страница 3: ...heater must be supported by materials having a working load limit of at least 115 lbs To install the heater in an adequate free area to allow the products of combustion to freely escape from the heat...

Страница 4: ...he control compartment air passageways and burner of the heater be kept clean If any changes are made to the patio or building structure after the heaters are installed such as adding plastic curtains...

Страница 5: ...ust be installed in accordance with ANSI NFPA 409 latest edition Standard for Aircraft Hangars ANSI NFPA 88a latest edition Standard for Parking Structures and ANSI NFPA 88b latest edition Standard fo...

Страница 6: ...ustibles are defined as a surface temperature of 117 F above ambient temperature OUTDOOR Spaces are defined as a shelter no more inclusive than a with walls on all sides but with no overhead cover b w...

Страница 7: ...the sign is posted in a location where it is easily accessed Clearances to combustibles are posted on the heater In areas used for storage of combustible materials where they may be stacked below the...

Страница 8: ...siding canvas tri ply etc may be subject to degradation at lower temperatures It is the installer s responsibility to assure that adjacent materials are protected from degradation See below the possib...

Страница 9: ...siding canvas tri ply etc may be subject to degradation at lower temperatures It is the installer s responsibility to assure that adjacent materials are protected from degradation See below the possi...

Страница 10: ...Electrical Supply Current Rating Weight Natural or Propane NPT Male 120 Volt 60Hz 1 Phase 0 1 Amp 55 lbs Module Electrical Rating Ignition System direct spark Input Control 18 30 VAC 50 60 Hz class 2...

Страница 11: ...60 degree Radiant output reduction 3 13 29 50 5 It is recommended to place the heaters in the area of greatest heat loss facing into the patio area The table below shows minimum area coverage per heat...

Страница 12: ...stance D for angled heaters applies when they are facing towards each other Note Local codes may have special requirements regarding head clearance requirements Some local codes require all portions o...

Страница 13: ...optional accessories available for the Wind Blocker Patio heater PN Description Picture 44560350 Wall Ceiling Telescopic Mounting Bracket Kit 15 22 overhead space check clearances to combustibles spac...

Страница 14: ...Mount Bracket Kit 10 fixed installation for minimum overhead clearance This bracket is only for horizontal mounting with the heat shield 44566300 Heat Shield Kit Reduced clearances to combustible opti...

Страница 15: ...Care must be taken when up packing the heater Carefully open the top of the heater as indicated on the labels at the side of the shipping box An angle gauge is attached to the heater s control side wi...

Страница 16: ...pan between supporting beams f The appliance should be located with respect to building construction and other equipment to permit access to the appliance for servicing etc f The heater must be instal...

Страница 17: ...er angle if needed Note If a heat shield is installed its location must match the heaters angle see Section 21 0 This process must be repeated for both ends of the heater INDOOR INSTALLATION HANGING M...

Страница 18: ...range of lengths and approved mounting angles of 150 300 450 and 600 44560350 KIT BRACKET WALL CEILING 15 22 CEILING FOR USE WITH HEAT SHIELD telescoping 44560351 KIT BRACKET CEILING 22 30 FOR USE WI...

Страница 19: ...angle and whether a heat shield is installed 15 22 Bracket With heat shield telescope hole positions 22 30 Bracket Without heat shield telescope hole positions Mounting Angle INDOOR OUTDOOR INDOOR OUT...

Страница 20: ...inimum working load of 115lbs 12 3 2 HEATER ATTACHMENT TO HANGING BRACKETS The heater can be attached to the hanging brackets in angles of 150 300 450 and 600 Choose the desired heater mounting angle...

Страница 21: ...UT 2 4 02352000 PHSMS 8 x 1 2 AB POINT SS BLK OXIDE 8 5 44568139 RAIL HEAT SHIELD HANGER PAINTED 1 6 44566189 HEAT SHIELD ROLLED PAINTED 1 7 44568149 HOLDER BRACKET PAINTED 2 8 43247112 LABEL INDOOR C...

Страница 22: ...eld hanger rail to the holder bracket using 2 black oxide 8 screws on each end Horizontal position shown below IMPORTANT Use the Acorn nuts at the control end of the heater as shown in the illustratio...

Страница 23: ...ERAMIC GLASS 14 0 Only install the ceramic glass once the heater has been attached to a suitable gas see Section 15 0 electrical supply see Section 16 0 and has been commissioned see Section 18 0 Read...

Страница 24: ...der the Glass Retainer at the heaters control enclosure side At this point the glass will be flush with the heater at the insertion point Note If the ceramic glass does not slide in easily review posi...

Страница 25: ...of the heater h The gas pipe flexible hose and connections must be self supporting The gas pipe work must not bear any of the weight of the heater or any other suspended assembly i This appliance is e...

Страница 26: ...UCTIONS FOR PRESSURE TEST GAUGE CONNECTION 15 1 INLET GAS PRESSURE CHECK 15 2 1 The installer will provide a 1 8 N P T tapped plug accessible for test gauge connection immediately upstream of the gas...

Страница 27: ...e solenoid Do not energize the HI solenoid 2 Remove regulator cover screw from the low outlet pressure regulator see Figure 1 below and turn screw clockwise to increase pressure or counterclockwise to...

Страница 28: ...r shall be connected to a permanently live electrical circuit one that is not controlled by a light switch 4 The power supply to the unit should be protected with a fused disconnect switch or circuit...

Страница 29: ...below shows the internal wiring diagram of the heater and the optional external connections depending on how the heater will be controlled FIELD CONNECTIONS AND WIRING DIAGRAMS 2 STAGE 24V 16 2 The f...

Страница 30: ...44201460 30 Mar 2019 A LOW VOLTAGE 24V 3 POSITION SWITCH CONNECTIONS SINGLE HEATERS B LOW VOLTAGE 24V 3 POSITION SWITCH CONNECTIONS MULTIPLE HEATERS C LOW VOLTAGE 24V THERMOSTAT CONNECTIONS SINGLE HEA...

Страница 31: ...The figure below shows the internal connection to operate the heater turning on and off 24V power to the heater with a permanent live power supply Important To operate the heater as single stage a jum...

Страница 32: ...GLE STAGE 120V 16 4 The figure below shows the internal connection to operate the heater turning on and off 120V power to the heater Important To operate the heater as single stage with 120V all three...

Страница 33: ...d and the minimum vent flow required is as follows WB35 N2and L2 140 cfm The General Ventilation Rules outlined in ASHRAE GUIDE AND DATA BOOK should be observed when locating vents Exhaust vents must...

Страница 34: ...occurs after successful ignition the appliance will attempt one re ignition before going to Lockout conditions 9 To shut down the appliance for short periods of time switch off the electrical supply t...

Страница 35: ...door Clearances to Combustibles Check that the area has not been closed in making it an indoor installation If any changes have been made then the clearances and ventilation requirements for Indoor in...

Страница 36: ...rt or debris including spider webs Foreign Objects Check and remove any foreign objects that are logged between the heat shield and the heater Ceramic Glass Clean the glass from the inside and outside...

Страница 37: ...Form 44201460 37 Mar 2019...

Страница 38: ...logo emblem s final position to be at the control side of the heater 4 2 Slide the glass into the Glass Retainer Rails The glass must be held parallel to the Glass Retainer Rails during assembly The...

Страница 39: ...Remove any foreign matter from the electrode tips and check that the spark gap is 199 5mm If the electrode flame sensor rods are badly oxidized replace the electrode flame sensor in the reverse order...

Страница 40: ...is removed from the illustration for clarity Loosen the panel nut 1 using a 19mm end wrench and remove from the gas valve manifold 2 Disconnect the wires to the gas valve 3 Remove the 4 screws from t...

Страница 41: ...e it from the heater 3 Disconnect the transformer lead wires Remove the screws 3 holding the transformer and remove it from the heater REMOVAL OF MAIN BURNER EMITTER ASSEMBLY 21 6 A Remove the ceramic...

Страница 42: ...Form 44201460 42 Mar 2019 INSTALLATION DATA 22 0 Date of Installation Number of Heaters in System Heater Serial Number Heater Model R B S W35 N Natural Gas L Propane Gas...

Страница 43: ...Module Fenwal 35 602906 915 1 Burner and Frame Components 1g 02132060 Rivet 1 8 x 294 SS grip range 188 250 not shown 10 1c 02168050 PHMS 10 24 x 3 8 SS 6 15 44555100 Support Plate Venturi 1 16 44570...

Страница 44: ...Please order by Part Number not by Item Number Refer to complete Model Number when ordering All replacement parts prices are available when ordering MODEL NUMBER SUFFIXES N2 Natural Gas L2 Propane Gas...

Страница 45: ......

Отзывы: