Form 44201460
31
Mar 2019
D.
LOW VOLTAGE (24V) THERMOSTAT CONNECTIONS - MULTIPLE HEATERS
FIELD CONNECTIONS AND WIRING DIAGRAMS – SINGLE STAGE 24V
16.3)
The figure below shows the internal connection to operate the heater turning on and off 24V power to the heater
with a permanent live power supply.
Important: To operate the heater as single stage a jumper wire must be installed across the 24V LO and HI
terminals as shown below. The heater will not operate with only 24V power to the HI terminal.