19
Mercedes-Benz Wallbox
| Error detection and solutions
Settings for the S1 and S3 rotary encoders
The following settings can be selected using the S1 rotary encoder on the
left
:
0
Normal operation
Setting for normal charging operations
1
no function
-
2
Testing mode
Measuring voltage (contactor closed) and communications (CP) possible at the charging contacts in order
to test functionality without a vehicle
3
Setting device ID
Device ID input possible via S3 rotary encoder (see next page)
4
Testing mode
See position 2
5
Setting the maximum charging current
8 A
6
10 A
7
13 A
8
16 A
9
20 A
A
30 A
B
32 A
C
64 A
D
Return to factory setting (16 A)
E
Testing mode
See position 2
F
Normal operation
Setting for normal charging operations
The following settings can be selected using the S3 rotary encoder on the
right
:
0
Normal operation
Setting for normal and testing operations
1
0x01
When the S1 rotary encoder is set to position 3 (see above) you can allocate the wallbox a different
device ID using the positions of the S3 encoder. Changing the device ID is intended for future
applications and currently does not affect the operation of the wallbox. It is therefore recommended
not to make any changes and to generally leave the S3 rotary encoder in the 0 position.
2
0x02
3
0x03
4
0x04
5
0x05
6
0x06
7
0x07
8
0x08
9
0x09
A
0x0A
B
0x0B
C
0x0C
D
0x0D
E
0x0E
F
0x0F