85-03-01205
ML-SERIES FIREPLACE
Page
26
3.2.13
Clearances to Combustible Mantels
Non-combustible (marble, brick, stone, metal etc.) mantels can be installed at any desired height above the top convection air
opening. Any pre-existing combustible mantel must fall within the approved mantel profile chart.
WARNING:
Make proper use of this chart. Do not compromise the specifications contained in this chart.
Failure to adhere to proper clearances required to combustibles may cause spontaneous combustion of the mantel and may
result in a fire causing property damage, personal injury or loss of life.
NOTE:
For mantels that protrude more than 8 inches from the front surface of the fireplace use a rise and run of (1:1) to
calculate the required height to the mantel.
EXAMPLE:
You have a 12" mantel. To calculate the height above the convection air opening the equation
would be: (Depth of Mantel)
–
8” +
49
” = (Height above the floor of the fireplace)
12” –
8” +
49
” =
53
”
DO NOT deviate from this minimum clearance requirement. Doing so can lead to a severe fire hazard.
Figure 3-18 Mantel Clearances
MODEL
A
B
MIN. UNIT
BASE TO
8" MANTEL
MIN. UNIT
BASE TO
BOTTOM OF
MANTEL
ML39
45
40
ML47
47
42
ML54
49
44
ML60
49
44
ML72
51
46
Figure 3-19 Allowable Mantel Profile Chart
Содержание ML39- AA-11-04391
Страница 2: ...85 03 01205 ML SERIES FIREPLACE HOMEOWNER NOTES...
Страница 16: ...85 03 01205 ML SERIES FIREPLACE Page 16 Figure 3 10 Figure 3 9...
Страница 87: ...85 03 01205 ML SERIES FIREPLACE Page 87 ML72 Gas Train Assembly Parts...
Страница 94: ......
Страница 95: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...