37
LP GAS PRESSURE REQUIREMENTS
Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only accessible from the outer
left side of the fireplace. A qualified installer shall take pressure measurements at these ports to verify and set the correct
gas pressures during the LP Kit installation and before facia materials are installed over the front of this fireplace.
Manifold
pressure must
be taken at the “MANIFOLD PRESSURE" tap and inlet pressure at the "INLET PRESSURE" tap
with the
burner
operating
by a qualified installer.
DESIRED
INLET
PRESSURE
MINIMUM
INLET
PRESSURE
MAXIMUM
INLET
PRESSURE
MANIFOLD
OUTLET
PRESSURE
AIR SHUTTER
POSITION
L.P. GAS
11.0" W.C
.
(2.75 kPa)
11" W.C.
(2.75 kPa)
13.0" W.C.
(3.24 kPa)
10.0" W.C.
(2.5 kPa)
1/4" OPEN MIN.
(5 mm)
REGULATE THE FLAME HEIGHT TO "HIGH" POSITION. OUTLET GAS PRESSURES MAY VARY PLUS OR MINUS 5%.
LPG PROPER INPUT RATES:
With the proper orifices installed, as specified
above, this fireplace utilizing LP Gas will have a
maximum input rate of 40,000 Btu/Hr.
LEAK TESTING REQUIREMENTS
Prior to completing the conversion process
, c
heck
for gas leaks with soap and water solution at all
plumbing joints prior to placing this appliance into
operation. It is recommended that all gas-
plumbing joints, factory installed and field installed
are checked for leaks.
PILOT FLAME AND MAIN BURNER
RELATIONSHIP VERIFICATION
Prior to completing the conversion process, the
qualified service technician must, light the pilot
light and verify the relationship between the pilot light flames and the main burners. The pilot light flames directed towards
the propagation ports on the rear and front burner must overlap the propagation ports on the burners. The pilot light
flames must be a
minimum of ¾” long and must overlap the propagation ports on both the rear and front burners as
shown in the diagram, below. Verify that the burner tubes ignite quickly and the burner flames propagate smoothly along
the entire length of the burners.
PILOT FLAME LENGTH ADJUSTMENT
If the pilot light flame length is too short and the system does not maintain a standing pilot, a qualified installer may in-
crease the length of the pilot light flames to meet the two requirements: Minimum pilot light length to maintain a standing
pilot light and the pilot light flames must be long enough to overlap the front and rear burner ports.
Figure 1: Pressure Test Port
1" MIN.
1" MIN.
1" MIN.
Pilot Flame
must overlap
Burner Ports
Содержание FV44i-PF2
Страница 20: ...19...
Страница 21: ...20...
Страница 22: ...21...
Страница 23: ...22...
Страница 24: ...23...
Страница 25: ...24...
Страница 26: ...25...
Страница 27: ...26 PLACE SMALL COALS ON TOP OF FLOOR BRICK PANELS AND CLOSE TO GRATE BOTTOM TO SIMULATE A COAL BED...
Страница 33: ...32 FV 44i GAS IGNITION SYSTEM WIRING DIAGRAM...
Страница 48: ...47...
Страница 50: ...49 TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...