InfiniBand FDR Switch Platform Hardware User Manual
Mellanox Technologies
31
Figure 12: Connect Rail Slide to Rack Vertical support
6. Place the four bolts for the caged nuts within reach.
7. Put the shelf into place and screw the bolts into the nuts from step 3
8. Extend the rail slides to the rack vertical support and screw them to the rack using the
2 hole washers and lock washers. See Figure 12.
9. Tighten all of the screws to 7.7 Nm or 68 pound inches.
10. Insert 8 caged nuts for the faceplate in the exact locations shown in
Figure 13,“Inserting the Caged Nuts for the Faceplate”.
11. Install the filler panel directly below the shelf.
Figure 13: Inserting the Caged Nuts for the Faceplate
Shelf
1
6
5
4
3
2
7
8
9
Filler panel
Shelf
1
5
4
3
2
7
8
9
6
Place the
caged nuts
here.
Spine Side
Leaf Side
Place the
caged nuts
here.