n
The flow monitor must be installed
in such a way as to preclude
damage by outside force. It must
be ensured that the flow monitor
cannot be damaged. If necessary,
install an appropriate impact pro-
tection device.
n
External magnetic fields will influ-
ence the switch contact. Keep suf-
ficient distance to magnetic fields
(e.g. electric motors).
n
Piping, process connections or
supports made of ferromagnetic
material influence the magnetic
field of the device. Keep a space
of at least 100 mm to those mate-
rials (e.g. steel).
Requirements for the environmental
conditions when using UL Recog-
nized Components :
n
indoor use
n
altitude up to 2000 m
n
temperature -15°C to 100°C
n
max. relative humidity 80 % for
temperatures up to 31 °C
decreasing linearly to 50 % rela-
tive humidity at 40 °C
n
mains supply voltage fluctuations
up to +/-10 % voltage
n
overvoltage category II
n
pollution degree 2
5.3 Preparatory work
The following requirements must be
met during installation to ensure cor-
rect functioning of the flow monitor:
WARNING!
Danger due to incorrect
installation!
If the requirements listed above
are not observed when instal-
ling the flow monitor, dan-
gerous/hazardous conditions
may arise.
–
Do not install the flow mon-
itor as a supporting part in
a pipe system
–
Do not use the flow monitor
with quick-acting valves
–
Do not use the flow monitor
with solenoid valves
Installation position/direction of
flow
Fig. 5: Installation position/direction of
flow
Installation und initial startup
Preparatory work
03.09.2018
DWG Module BASICS Flow Monitor