Format of the ABB SPA Time String
The ABB SPA Time String is a sequence of 32 ASCII characters starting with the
characters ">900WD" and ending with the <CR> (Carriage Return) character. The
format is:
>900WD:
yy-mm-tt
_
hh.mm;ss.fff
:
cc
<CR>
The letters printed in
italics
are replaced by ASCII numbers whereas the other
characters are part of the time string. The groups of characters as defined below:
yy-mm-tt
the current date:
yy
year of the century
(00..99)
mm
month
(01..12)
dd
day of month
(01..31)
_
Space (ASCII code 20h)
hh.mm;ss.fff
the current time:
hh
hours
(00..23)
mm
minutes
(00..59)
ss
seconds
(00..59, or 60 while leap second)
fff
milliseconds
(000..999)
cc
Check sum. EXCLUSIVE-OR result of the previous characters, displayed as a
HEX byte (2 ASCII characters 0..9 or A..F)
<CR>
Carriage Return (ASCII code 0Dh)
130
Содержание LANTIME
Страница 1: ...Technical Information Operating Instructions LANTIME SHSPZF ETX BGT...
Страница 47: ...Configuration Ethernet 47...
Страница 52: ...Configuration Notification 52...
Страница 56: ...Configuration Security 56...
Страница 69: ...Configuration Local 69...
Страница 77: ...Configuration Statistics 77...
Страница 110: ...Rear View LANTIME 110...
Страница 111: ...SUB D Connector Assignments 111...
Страница 113: ...Accuracy of frequency TCXO quartz standard 113...
Страница 118: ...HUMIDITY Relativ humidity 85 max TEMPERATURE RANGE 0 60 Celsius POWER SUPPLY 5 V approx 330 mA 118...
Страница 132: ...Menu Quick Reference 132...
Страница 145: ...IRIG Standard Format 145...
Страница 146: ...AFNOR Standard Format 146...