53
download from the right-click menu to complete the setup.
6.3 the setting
Example: MTC station number is 2. Set the first channel to use mode 3, work in the heating mode, the
given value is 100.0
℃
, the control cycle is 3 seconds, use the self-tuning mode, the self-tuning deviation
is set to -20
℃
.
1. Refer to the 6.1 feature to change the first three steps for setting
2. Select the control function and set it according to the figure below.
Figure 6-9 setting the control function
3. Right-click the site 2 option under the module configuration in the left tree structure, and select
download from the right-click menu.
4. Click menu monitor -> to start monitoring.
5. Click chart monitor and select 1 from the self-tuning start/stop of the corresponding channel. Start,
click ok in the dialog box that pops up, wait a few seconds, self-tuning start/stop will change from stop to
start, start self-tuning, until finished, self-tuning start/stop will change from start to stop, the thermostat
will continue to run after self-tuning parameters.
Figure 6-10 Confirm start self - tuning
6.4 multi-step setting
Example: MTC station number is 2. The first channel is set to use mode 3, work in heating mode, control
cycle is 3 seconds, proportional band is 20, integral time is 60, differential time is 15. See table 6-1 for the