43
13
Wait again with
the deviation low
limit alarm
Alarm when the deviation (measured
value-set value) is greater than the alarm
set value, but the measured value will be
ignored when the power is turned on and
the set value changes
± input width
14
Wait again with
the
deviation
high/low
limit
alarm
When the absolute value of deviation (|
measured value - set value |) is larger
than the alarm setting value, the
measured value will be ignored when the
power is switched on and the set value
changes
± input width
Note
:
1
.
Input scope
:
The value between the lower input value and the upper input value. For example,
if the upper and lower limits are 100 and 1000 respectively, the range is 101
~
999.
2.Input width
:
Width from the lower limit to the upper limit of the input value (upper limit-lower limit). For
example, if the upper limit is 100 and lower limits is 1000, then "+ input width" is "0
~
900" and "± input
width" is "
-
900
~
900"
Basic alarm description
1
.
High limit
Alarm when the measured value (PV) is larger than the alarm setting
Figure 5-6 Schematic diagram of the
high limit
2
.
Low limit
Alarm when the measured value (PV) is smaller than the alarm setting
Figure 5-7 Schematic diagram of the low
limit
3
.
Deviation high
Alarm when the deviation value (= PV - SV) is larger than the alarm setting value