10
BFM
Content
Remarks
Natu
re
Sav
e
CH1 CH2 CH3 CH4
#201
Change Settings allowed*2 Default value
:
1
,
Allows to change
0
:
Not Allowed To Change
R/W
N
#801 #802 #803 #804 Digital filter set of one step Default value
:
0
Range
:
0
~
100
(
Seconds
)
R/W
Y
#809 #810 #811 #812 D0*3
Default value
:
0
R/W
Y
#817 #818 #819 #820 D1*3
Default value
:
12000
(
With the input
type change
)
R/W
Y
#825 #826 #827 #828 A0*3
Default value
:
0
R
N
#833 #834 #835 #836 A1*3
Default value
:
12000
(
With the input type change
)
R
N
* 1. After #200 is set to 1, all BFM units of the module are reset to their default values.
* 2. Change Settings allowed for BFM. Setting BFM#201 to 0 will prevent the user from making
inadvertent adjustments to BFM. Once the disable Settings feature is set, it remains in effect until the
allow command is set (#201 = 1).
* 3. #801 ~ #804: set the data cache D0 for each channel; #809 ~ #812: each channel feature sets the
data cache D1. Use the two-point method to set channel characteristics, D0, D1 represents the channel
output digital quantity, A0, A1 represents the channel actual input temperature value, each channel
occupies 4 words. Considering the convenience of the user's setting, and without affecting the realization
of the function, A0 was fixed as 0
℃
, and A1 was fixed as the maximum of the measurement range in the
current mode. If you change the D0 and D1 values of the channel, you can change the channel
characteristics. D0 and D1 can be adjusted
±
1000 on the basis of factory setting. If the current mode
uses Celsius, the adjustment range is
±
100
℃
; if the current mode uses Fahrenheit, the adjustment
range is
±
100
℉
. If a value is set beyond this range, the MTC will not accept it and will keep the original
valid setting.
1.5.3 control function setting
MTC-04-NVT buffer (BFM) set the control function of the content to table1-9.
Table 1-9 MTC-04-NVT buffer (BFM) the control function of the set
BFM
Content
Remarks
Nature
Save
CH1 CH2 CH3
CH4
#901 #902 #903 #904 Input type *1
Default value
:
0
R/W
Y
#909 #910 #911 #912 Set value (SV) * 2
Default value
:
0.0
Unit
:
0.1
℃
/
℉
R/W
Y
#917 #918 #919 #920 Control output cycle
set * 3
Default value
:
2
Range
:
1
~
100
R/W
Y
#925 #926 #927 #928 Heat side proportional
band
Default value
:
30
Unit
:
0.1
%
Range
:
0.1
%~
1000.0
%
R/W
Y
#933 #934 #935 #936
Heat side integrative
time
Default value
:
240
Range
:
1
~
3600
(
Seconds
)
R/W
Y
#941 #942 #943 #944
Heat side
Derivative
time
Default value
:
60
Range
:
0
~
3600
(
Seconds
)
R/W
Y
#957 #958 #959 #960 Cool side proportional
band
Default value
:
30
Unit
:
0.1
%
Range
:
0.1
%~
1000.0
%
R/W
Y
#965 #966 #967 #968
Cool side integrative
time
Default value
:
240
Range
:
1
~
3600
(
Seconds
)
R/W
Y