11
BFM
Content
Remarks
Nature
Save
CH1 CH2 CH3
CH4
#973 #974 #975 #976
Cool side
derivative
time
Default value
:
60
Range
:
0
~
3600
(
Seconds
)
R/W
Y
#981 #982 #983 #984 Overlap/Deadband*4
Default value
:
0
No overlapped
non-inductive belt
Setting range:-input
range~+input range
R/W
Y
#989 #990 #991 #992
Undershoot
suppression
factor*5
Water-cooled default
Air-cooled default
Range:0~1000
R/W
Y
#997
Control start/stop
setting of CH1-CH4 *6
Default value
:
B0000
0
:
Stop 1
:
Start
R/W
Y
M0
M1
M2
M3
Control action *6
Default value
:
B0000
0
:
Stop 1
:
Start
R/W
Y
#999
Auto-tuning setting of
CH1- CH4 *7
Default value
:
B0000
0:Not self-tuning or auto-t
uning has been completed
1
:
Auto-Tune
R/W
Y
M8
M9
M10
M11 Auto-tuning setting of
CH1- CH4 *7
Default value
:
0
0:Not self-tuning or auto-t
uning has been completed
1
:
Auto-Tune
R/W
Y
#1000 #1001 #1002 #1003 Control mode setting Default value
:
2
0
:
Hand 1
:
ON/OFF 3:PID R/W
Y
#1008 #1009 #1010 #1011 Heat / cool action*8
Default value
:
1
0:Cooling
1:Heating
2:Heating and cooling (air
cooling)
3:Heating and cooling
(water cooling)
4:Position ratio PID
R/W
Y
#1016 #1017 #1018 #1019 Manual output of set
values
Default value
:
0
Range
:
0.0
~
100.0
(%)
R/W
Y
#1024 #1025 #1026 #1027
Adjust sensitivity
Settings
(
ON/OFF
control method is
effective
)
Default value:100
Unit
:
0.1
℃
/
℉
Range
:
0~999
R/W
Y
BFM
Content
Remarks
Nature Save
CH1 CH2
CH3
CH4
#1032 #1033 #1034 #1035 Auto-tuning deviation
setting
Default value
:
0
Unit
:
0.1
℃
/
℉
Range:
±
input range
R/W
Y
#1101 #1102 #1103 #1104 Heat side proportional Default value
:
100%
R/W
Y