0.1mA/30Vdc
;
Minimum load
:
5mA
(
5Vdc
~
24Vdc
)
Sampling cycle
100ms or 1s(optional)
Control cycle
0.1
~
10 s or 1
~
100 s
,
default 0.2 s or 2 s
,
Determined
by the characteristics of the temperature control object
Control method
Manual control
,
ON/OFF control
,
PID contrpl,Heating
and cooling PID control
Rate
temperat
ure range
Type K
-
100
℃~
1200
℃(-
148
℉~
2192
℉)
Type J
-
100
℃~
1200
℃(-
148
℉~
2192
℉)
Type E
-
100
℃~
850
℃(-
148
℉~
1562
℉)
Type N
-
100
℃~
1200
℃(-
148
℉~
2192
℉)
Type T
-
200
℃~
300
℃(-
328
℉~
572
℉)
Type R
0
℃~
1600
℃(
32
℉~
2912
℉)
Type S
0
℃~
1600
℃(
32
℉~
2912
℉)
Type B
400
℃~
1800
℃(
752
℉~
3272
℉)
Pt100
-
150
℃~
600
℃(-
238
℉~
1112
℉)
JPt100
-
150
℃~
500
℃(-
238
℉~
932
℉)
Cu100
-
30
℃~
120
℃(-
22
℉~
248
℉)
Cu50
-
30
℃~
120
℃(-
22
℉~
248
℉)
Ni120
-
80.0
℃~
280.0
℃(-
112.0
℉~
536.0
℉)
Accuracy
Thermocouple
Input range
±
0.3
%,
Ambient temperature
compensation error<=2
℃
Thermal resistance
Input range
±
0.5
%
Isolation
The sampling channel is isolated from the power supply,
the sampling channel is isolated from the output, and
the channels are not isolated from each other
Note
: 1. Through the appropriate input type selection Settings, two kinds of data can be
obtained:
℃
and
℉
.
2. Standard for thermocouple and thermal resistance:
K, J, E, N, T, R, S, BIEC 60584-1-1995
PT100
IEC60751 - AM2-1995
JPT100
JIS C1604-1997
Cu100, Cu50 JJG 229-1998
1.5 Buffer description
MTC-04-NVT and the main module exchange information through the buffer (BFM), using
Modbus or MCbus. The cache that reads and writes properties can use MODBUS or MCBUS
instructions to write and read the contents of any cell in the BFM region. If the reserved cell is
read, it will get a value of 0. Save mark as Y represents the use of parameter save function, can be
written to flash, mark as N means can not be written to flash. The content of the BFM unit is as
follows:
1. Channel operation monitoring.
2. Channel feature setting.