Start-up
25
The relevant individual parameters for disconnecting and reclosing the power modules
can be defined in the menu
Settings
Fuse
(they can also be accessed by
clicking on the fuse value in the main screen).
The operating parameters can also be adapted during operation at any time,
either directly on the supply module or remotely.
A change to the parameters does not influence the switching state of the power
switch.
The following parameters are configurable:
Parameter
Description
Fuse thresholds
Fuse rating
Here the rated current is to be set according to the replaced
fuse.
When the current set here is exceeded for a certain amount
of time, the power switch automatically turns off and
disconnects the protected LV distribution line from the
supply network.
Warning threshold
Current value above which a warning is displayed in the
main menu and, depending on the notification settings (see
page 49), when desired a notification is sent. The warning
threshold monitoring can be activated/deactivated via the
switch.
Reclose
PM-A | PM-B | PM-C
Activate/deactivate automatic reclosing for the connected
power modules individually
Count (x)
Number of automatic reclosing operations until final
shutdown.
If the slide is pushed to all the way to the right, the number
of automatic reclosures is unlimited.
If this setting is changed during operation, the counter for
the previously performed reclosing operations is reset.
Pause (sec.)
Wait time in seconds after which the power switch turns
back on independently.
The settings must then be saved using the
button.
Configuring the
shutdown and reclose
behaviour