92
Figure 67: CT Burden Test Abort
13.
Test can also be stopped under emergency condition by hitting the “Emergency Push to Stop”
button on the front panel of MRCT. Unit will shut off the output voltage
14.
After releasing the Emergency Stop Button, the test will need to be restarted.
15.
Upon completion of all tests the results will be displayed in the test screen or in a
test report.
Figure 68: CT Burden Test Results Screen
Burden test is performed to verify that CT under test is capable of supplying a known current into a
know burden while maintaining its stated accuracy. A burden test is typically performed at full rated
secondary current value. Burdens are typically expressed in VA
X Current (A): It displays the applied current (user selected 1A or 5A) to the burden of the CT.