Figure 33: Run All Tests - Configuration
10.
Select the individual taps for saturation testing by placing a check in the corresponding
box. Or select all taps by selecting the
button. This will place a check
corresponding to all taps.
11.
Select the individual taps for ratio testing by placing a check in the corresponding
box. Or select all taps by selecting the
button. This will place a check
corresponding to all taps.
12. Select the individual taps for Winding Res testing by placing a check in the corresponding
box. Or select all taps by selecting the
button. This will place a check
corresponding to all taps.
13.
Place a check in the corresponding box next to each desired insulation test – Primary to
Secondary, Primary to Ground, and Secondary to Ground.
14.
Select the desired voltage range to conduct the insulation test; either 500V or 1KV
15.
At this point, this test file could be saved, opened at a later date , and ran.