69
Figure 44: Saturation Test Screen Non Concurrent
15.
The test can also be stopped under emergency condition by hitting the “Emergency Push to
Stop” button on the front panel of MRCT. Unit will shut off the output voltage
16.
After releasing the Emergency Stop Button, the test will need to be restarted
17.
Upon completion of test the results will be displayed in the test screen or it can be displayed
in a test report by selecting the view report button
18.
Saturation points: The unit automatically determines the knee point based upon the
user selected standard (ANSI 30, ANSI 45 or IEC 60044-1). Saturation voltage and
saturation current corresponding to that knee point are displayed along with other
results at the completion of the test.
9.3 CT Ratio Test
9.3.1 Method 1 – Concurrent
Connections for the test set:
Refer to the safety instructions first before use of the equipment.
1.
Verify the Power ON/OFF switch is OFF. Power the test set from a suitable source of power (95-265
V50/60 Hz).
2.
Connect the ground wing nut to a suitable ground.