IDAX User's Manual
6
© 2009 Megger AB
1.1.3
Safety Precautions
A "
Warning
" statement denotes hazardous conditions and actions that can cause bodily
harm or death.
A "
Caution!
" statement denotes conditions and actions that can damage the IDAX or the
equipment being tested.
Warning!
Always follow local safety regulations when working on high voltage equipment.
Make certain all personnel working with IDAX have been trained in its correct use
and that all applicable safety precautions are taken.
BEFORE connecting this unit to the mains outlet user must verify that only a single
protective ground systems exists AND no measurable voltage potential exists
between the mains outlet protective ground and the test object protective ground. If
a voltage potential is found between mains outlet protective ground and the test
object protective ground then additional measures described in local safety standards
should be applied to ensure personal safety.
The measurement system can generate hazardous and even lethal voltages.
Do not attempt to service the IDAX yourself as opening or removing covers may
expose you to dangerous voltage.
Do not use any accessories that are not intended for use together with the IDAX.
Unplug the IDAX from the mains supply when it is left unattended or not in use.
Before cleaning, unplug the IDAX from the mains supply. Use a damp cloth for
cleaning. Do not use liquid or aerosol cleaners.
Caution!
Make sure that the mains voltage selected on the selector switch located on the back
panel corresponds to the voltage level before connecting the mains.
Refer all servicing to qualified service personnel.
If you need to return your IDAX, please use either the original crate or one of
equivalent strength.
Содержание IDAX Series
Страница 1: ...2009 Megger AB IDAX User s Manual...