background image

Note: There is a short delay

on the first operation of
‘1000V’ range, each
time the range is
selected. This is to
prevent accidental
application of 1kV.

The M

range features a

leakage current display.
Leakage current is the value
of current that flows during
the insulation test. To view
the leakage current press the

key. To view insulation resistance press the        key

again.

Good Procedure Whilst Insulation Testing
Care must be taken when taking measurements greater than a
few G

. The leads must be clean dry and in good condition.

They must also not be allowed to tangle. It is also advisable
that the switched probe SP1 is not used as the accuracy at
high value measurements is not guaranteed. The instrument
should also be clean and dry with particular attention paid to
the terminals. Also attempt to reduce any leakage that may
give erroneous results on the item under test.

Polarisation Index Testing
Polarisation Index (PI) is the term applied to the Dielectric
Absorption Ratio when resistance values are measured after
1 minute and again after 10 minutes. Polarization Index is then
the resistance value after 10 minutes divided by the resistance
value after 1 minute. The test can be run at any voltage. More
detailed information on PI Testing and value assessment can
be found in Megger Limited publications listed in the
Accessories page.

Automatic Discharge
When the TEST button is released after an insulation test (or
re-pressed if 

ltb feature is enabled), a 200k

load is

automatically switched across the terminals to discharge the
item under test. Any voltage present will be indicated on the
display so that the discharge can be monitored. 

TYPICAL TERMINAL VOLTAGE CHARACTERISTICS

FIG.1

50V - 1000V Ranges

10V Range

Содержание BMM2000 Series

Страница 1: ...ave no broken or cracked insulation Ensure that hands remain behind guards of probes clips when testing U K Safety Authorities recommend the use of fused test leads when measuring voltage on high ener...

Страница 2: ...Regulations IEC364 and HD384 since each range has a 1mA minimum test current at the minimum pass values of insulation specified in these documents The 100V range is ideal for testing telecommunication...

Страница 3: ...is activated by pressing the key The backlight will remain illuminated for approx one minute before automatically switching off to conserve battery life alternatively the key can be re pressed Insula...

Страница 4: ...paid to the terminals Also attempt to reduce any leakage that may give erroneous results on the item under test Polarisation Index Testing Polarisation Index PI is the term applied to the Dielectric A...

Страница 5: ...ation is retained in non volatile memory and so will be remembered when the instrument is switched off 1 Select the Continuity range 2 Short the test leads across a known good conductor using prods 3...

Страница 6: ...ent The diode symbol will appear if the voltage developed across the terminals is within semi conductor junction limits These features together with the small test current and wide measurement range 0...

Страница 7: ...icate the zero has been adjusted 1 Select the uF range 2 Disconnect the test leads from the circuit under test 3 When the reading has stabilised press the TEST button The zero offset symbol will appea...

Страница 8: ...he user should the probe be used accidentally in conjunction with a test lead in the low terminal Relates to transient overvoltage likely to be found in fixed installation wiring Do not use the probe...

Страница 9: ...digits 0 8 per G 100V 20G 2 2 digits 2 0 per G 50V 10G 2 2 digits 4 0 per G Accuracy BMM2000 Range Full Scale Accuracy 1000V 20G 2 2digits 0 2 per G 500V 10G 2 2 digits 0 4 per G 250V 5G 2 2 digits 0...

Страница 10: ...460 Hz 5 7 digits 10mV to 1999mV a c 16 460 Hz 5 5 digits d c milliVolts zeroing Up to 9 9mV Input resistance 3M Capacitance BMM2080 Measuring Range 0 1nF to 9 99uF Accuracy 3 2 digits 0 2nF uF zeroin...

Страница 11: ...imit Min Indicated Limit Min Indicated Reading Reading 0 10 0 14 2 00 2 12 0 20 0 25 3 00 3 16 0 30 0 35 4 00 4 20 0 40 0 46 5 00 5 24 0 50 0 56 10 00 10 8 0 60 0 66 20 00 21 2 0 70 0 77 30 00 31 6 0...

Страница 12: ...sec 500V insulation tests 4000 5 sec 250V insulation tests 2700 5 sec continuity tests 4700 5 sec k tests ENVIRONMENTAL CONDITIONS Operating range 5 to 40 C Operating humidity 90 RH at 40 C max Stora...

Страница 13: ...contact Megger Limited or Megger Archcliffe Road Valley Forge Corporate Center Dover 2621 Van Buren Avenue Kent CT17 9EN Norristown PA 19403 England U S A Tel 44 0 1304 502243 Tel 1 610 676 8500 Fax 4...

Страница 14: ...rporate Center 2621 Van Buren Avenue Norristown PA 19403 Tel 1 610 676 8500 U S A Fax 1 610 676 8610 Megger Z A Du Buisson de la Couldre 23 rue Eug ne Henaff T 33 1 30 16 08 90 78190 TRAPPES France F...

Отзывы: