SPECIFICATION

(All quoted accuracies are at +20°C.)

Insulation Ranges
Nominal Test Voltage (d.c.):
BMM2080:

50V, 100V, 250V, 500V, 1000V

BMM2000:

250V, 500V, 1000V

BMM2000ESD:

10V, 100V, 500V

Test voltage accuracy: 

1000V, 500V, 250V, 100V, 50V,
+15% maximum on open circuit.
10V, ±10% maximum on open
circuit.

Short circuit current: 

< 2 mA

Test Current on load:

1mA at min. pass value of
insulation specified in BS7671,
HD384 and IEC364, 2mA max.

Accuracy (BMM2080)

Range Full 

Scale  Accuracy

1000V 200G

±2% ±2digits ±0,2% per G

500V 100G

±2% ±2 digits ±0,4% per G

250V 50G

±2% ±2 digits ±0,8% per G

100V 20G

±2% ±2 digits ±2,0% per G

50V 10G

±2% ±2 digits±4,0% per G

Accuracy (BMM2000)

Range Full 

Scale  Accuracy

1000V 20G

±2% ±2digits ±0,2% per G

500V 10G

±2% ±2 digits ±0,4% per G

250V 5G

±2% ±2 digits ±0,8% per G

Accuracy (BMM2000ESD)

Range Full 

Scale  Accuracy

500V 10G

±2% ±2digits ±0,4% per G

100V 2G

±2% ±2 digits ±2,0% per G

10V 1G

±2% ±2 digits ±2,0% per 100M

Note: Above specifications only apply when high quality silicone

leads are being used.

Measuring Range:

0,01M

to 200G

(0-100G

on analogue scale). 

EN61557 Operating range: 0,10M

to 1,00G

Leakage Current:

10% ±3digits

Continuity 

Measuring Range: 

0,01

to 99,9

(0-10

on analogue scale)

EN61557 Operating range: 0,10

to 99,9

Accuracy: 

±2% ±2 digits

Open circuit voltage: 

5V ±1V

Test current: 

210mA ±10mA (0-2

)

Содержание BMM2000 Series

Страница 1: ...ave no broken or cracked insulation Ensure that hands remain behind guards of probes clips when testing U K Safety Authorities recommend the use of fused test leads when measuring voltage on high ener...

Страница 2: ...Regulations IEC364 and HD384 since each range has a 1mA minimum test current at the minimum pass values of insulation specified in these documents The 100V range is ideal for testing telecommunication...

Страница 3: ...is activated by pressing the key The backlight will remain illuminated for approx one minute before automatically switching off to conserve battery life alternatively the key can be re pressed Insula...

Страница 4: ...paid to the terminals Also attempt to reduce any leakage that may give erroneous results on the item under test Polarisation Index Testing Polarisation Index PI is the term applied to the Dielectric A...

Страница 5: ...ation is retained in non volatile memory and so will be remembered when the instrument is switched off 1 Select the Continuity range 2 Short the test leads across a known good conductor using prods 3...

Страница 6: ...ent The diode symbol will appear if the voltage developed across the terminals is within semi conductor junction limits These features together with the small test current and wide measurement range 0...

Страница 7: ...icate the zero has been adjusted 1 Select the uF range 2 Disconnect the test leads from the circuit under test 3 When the reading has stabilised press the TEST button The zero offset symbol will appea...

Страница 8: ...he user should the probe be used accidentally in conjunction with a test lead in the low terminal Relates to transient overvoltage likely to be found in fixed installation wiring Do not use the probe...

Страница 9: ...digits 0 8 per G 100V 20G 2 2 digits 2 0 per G 50V 10G 2 2 digits 4 0 per G Accuracy BMM2000 Range Full Scale Accuracy 1000V 20G 2 2digits 0 2 per G 500V 10G 2 2 digits 0 4 per G 250V 5G 2 2 digits 0...

Страница 10: ...460 Hz 5 7 digits 10mV to 1999mV a c 16 460 Hz 5 5 digits d c milliVolts zeroing Up to 9 9mV Input resistance 3M Capacitance BMM2080 Measuring Range 0 1nF to 9 99uF Accuracy 3 2 digits 0 2nF uF zeroin...

Страница 11: ...imit Min Indicated Limit Min Indicated Reading Reading 0 10 0 14 2 00 2 12 0 20 0 25 3 00 3 16 0 30 0 35 4 00 4 20 0 40 0 46 5 00 5 24 0 50 0 56 10 00 10 8 0 60 0 66 20 00 21 2 0 70 0 77 30 00 31 6 0...

Страница 12: ...sec 500V insulation tests 4000 5 sec 250V insulation tests 2700 5 sec continuity tests 4700 5 sec k tests ENVIRONMENTAL CONDITIONS Operating range 5 to 40 C Operating humidity 90 RH at 40 C max Stora...

Страница 13: ...contact Megger Limited or Megger Archcliffe Road Valley Forge Corporate Center Dover 2621 Van Buren Avenue Kent CT17 9EN Norristown PA 19403 England U S A Tel 44 0 1304 502243 Tel 1 610 676 8500 Fax 4...

Страница 14: ...rporate Center 2621 Van Buren Avenue Norristown PA 19403 Tel 1 610 676 8500 U S A Fax 1 610 676 8610 Megger Z A Du Buisson de la Couldre 23 rue Eug ne Henaff T 33 1 30 16 08 90 78190 TRAPPES France F...

Отзывы: