background image

Live Circuit Warning
When more than 25V (10V on 10V insulation range) is applied
to the terminals in the insulation ranges, the instrument defaults
to a voltmeter and gives an audible warning if a test is
attempted.On all other switch positions except OFF/V when
approx 10V is applied the default voltmeter will be activated.
Testing will be inhibited. 

Voltage Testing on High Energy Systems
Use extreme care when using or measuring voltages above
30V, particularly in high energy systems. Fused test leads are
available as optional accessories for local situations where
increased protection is required.

Auto-shut Off
To conserve battery life, Auto-shut Off (preceded by a series of
bleeps) operates after approx. 10 minutes of instrument
inactivity on insulation, 5 minutes on all other ranges. If the
instrument is switched on whilst holding the

key, the

Auto shut-off time is extended to 60 minutes. To restore
operation after Auto-shut Off, either select OFF followed by the
required switch position.

Note: It is recommended that the instrument is switched to the

OFF position when not in use. 

Backlight
The backlight is activated by pressing the

key. The

backlight will remain illuminated for approx. one minute before
automatically switching off to conserve battery life, alternatively
the

key can be re-pressed.

Insulation Tests (M

(See fig. 1)

The insulation tests apply a known voltage to the circuit under
test and measure the resulting leakage current. The circuit
under test must be completely de-energised and isolated
before test connections are made.

Insulation tests are only initiated when the TEST button is
pressed.
1.  Set the range switch to the test voltage required.
2.  Connect the test leads, first to the instrument, and then to

the isolated item under test.

3. Press 

the 

TEST button to activate the test voltage. Take

the reading.

4.

Release the TEST button at the end of the test. 

5.  Any capacitive circuits charged during a test will automatically

discharge. If significant voltage remains the voltage warning
will occur and the voltage present displayed.

6.  Remove the test leads only when no voltage is indicated.

Locking Test Button (ltb)
When it is desired to do a long insulation test, the test can be
‘locked on’ by pressing the

key while the test button is

held down. The warning

will appear on the display and

both buttons may be released whilst the test continues. The
next press of the test button will terminate the test.

~

~

Содержание BMM2000 Series

Страница 1: ...ave no broken or cracked insulation Ensure that hands remain behind guards of probes clips when testing U K Safety Authorities recommend the use of fused test leads when measuring voltage on high ener...

Страница 2: ...Regulations IEC364 and HD384 since each range has a 1mA minimum test current at the minimum pass values of insulation specified in these documents The 100V range is ideal for testing telecommunication...

Страница 3: ...is activated by pressing the key The backlight will remain illuminated for approx one minute before automatically switching off to conserve battery life alternatively the key can be re pressed Insula...

Страница 4: ...paid to the terminals Also attempt to reduce any leakage that may give erroneous results on the item under test Polarisation Index Testing Polarisation Index PI is the term applied to the Dielectric A...

Страница 5: ...ation is retained in non volatile memory and so will be remembered when the instrument is switched off 1 Select the Continuity range 2 Short the test leads across a known good conductor using prods 3...

Страница 6: ...ent The diode symbol will appear if the voltage developed across the terminals is within semi conductor junction limits These features together with the small test current and wide measurement range 0...

Страница 7: ...icate the zero has been adjusted 1 Select the uF range 2 Disconnect the test leads from the circuit under test 3 When the reading has stabilised press the TEST button The zero offset symbol will appea...

Страница 8: ...he user should the probe be used accidentally in conjunction with a test lead in the low terminal Relates to transient overvoltage likely to be found in fixed installation wiring Do not use the probe...

Страница 9: ...digits 0 8 per G 100V 20G 2 2 digits 2 0 per G 50V 10G 2 2 digits 4 0 per G Accuracy BMM2000 Range Full Scale Accuracy 1000V 20G 2 2digits 0 2 per G 500V 10G 2 2 digits 0 4 per G 250V 5G 2 2 digits 0...

Страница 10: ...460 Hz 5 7 digits 10mV to 1999mV a c 16 460 Hz 5 5 digits d c milliVolts zeroing Up to 9 9mV Input resistance 3M Capacitance BMM2080 Measuring Range 0 1nF to 9 99uF Accuracy 3 2 digits 0 2nF uF zeroin...

Страница 11: ...imit Min Indicated Limit Min Indicated Reading Reading 0 10 0 14 2 00 2 12 0 20 0 25 3 00 3 16 0 30 0 35 4 00 4 20 0 40 0 46 5 00 5 24 0 50 0 56 10 00 10 8 0 60 0 66 20 00 21 2 0 70 0 77 30 00 31 6 0...

Страница 12: ...sec 500V insulation tests 4000 5 sec 250V insulation tests 2700 5 sec continuity tests 4700 5 sec k tests ENVIRONMENTAL CONDITIONS Operating range 5 to 40 C Operating humidity 90 RH at 40 C max Stora...

Страница 13: ...contact Megger Limited or Megger Archcliffe Road Valley Forge Corporate Center Dover 2621 Van Buren Avenue Kent CT17 9EN Norristown PA 19403 England U S A Tel 44 0 1304 502243 Tel 1 610 676 8500 Fax 4...

Страница 14: ...rporate Center 2621 Van Buren Avenue Norristown PA 19403 Tel 1 610 676 8500 U S A Fax 1 610 676 8610 Megger Z A Du Buisson de la Couldre 23 rue Eug ne Henaff T 33 1 30 16 08 90 78190 TRAPPES France F...

Отзывы: