21
5
Num
Flag
Object
Function
Length
DPT
Function
Description
21
22
23
24
[Dali B]
Activate
Test Mode
[Dali B]
Dali Power
Failure
[Dali B]
Dali Short
Circuit
[Dali B]
ECG
Presence
Start/Stop
(DPT1.010)
Alarm
(DPT1.005)
Alarm
(DPT1.005)
Alarm
(DPT1.005)
1 bit
1 bit
1 bit
1 bit
CW
CRT
CRT
CRT
Activate/Stop
0 = No Error;
1 = Error
0 = No Error;
1 = Error
0 = No Error;
1 = Error
DALI Bus B - Test
mode.
Activates or
deactivates the test
mode via the bus.
Note: This object is
only valid when the
parameter “ECG
Types” chose Self
Contained Battery
Lamp.
Reports the
presence of DALI
bus voltage
abnormal in the
connected DALI
segment.
Reports the
presence of a DALI
short-circuit in the
connected DALI
segment.
Reports the
presence of an ECG
disconnect in the
connected DALI
segment.
22
5
Num
Flag
Object
Function
Length
DPT
Function
Description
25
26
27
[Dali B]
ECG
Diagnostics
[Dali B]
On/Off
(Status
Group 1 –
Gruop16)
[Dali B]
On/Off
(Status
ECG1-ECG
16)
Diagnostics
value
(DPT 238.600)
Bit-combined
info on/off
(DPT 27.001)
Bit-combined
info on/off
(DPT 27.001)
1 bytes
4 bytes
4 bytes
CRT
CRT
CRT
ECG
Diagnostics
Status
Status
This object is used
to send the error
status of lamp or
ECG errors in the
DALI segment when
the system is
started or when a
change has taken
place. Bit 0 - 5 refer
to the number of the
ECG, range from 0 -
63. Bit 6 represents
a lamp error, Bit 7
an ECG error, 0 = no
error; 1 = error.
Sends the on/off
status for groups 1 -
16. Bit 0 -15 refer to
Group 1 to Group
16. For example:
Sends the on/off
status for ECG 1 -
16. Bit 0 -15 refer to
ECG 1 to ECG 16.
For example:
Grp.16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Grp.16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Group 3 on: 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
Group 3 on: 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0