3.4.2 Physical Address Assignment
To commission the device an interface connection (IP, USB) to the KNX bus system
is required. The device is supplied with the individual physical address 15.15.0. The
KNX product database entry (available for ETS4 and higher) can be downloaded
from the Meanwell website and from the KNX Online Catalog.
With the ETS the physical address can be assigned to the device by setting the
desired address in the properties window of the ETS. After starting the ETS
download and then pressing the Program Button the device restarts itself.
Figure 4: ETS Properties Window
Note: In this document only the term “physical address” is used. The term “physical
address” means the KNX physical address as well as the ETS individual address.
Both terms are used by the KNX organisation interchangeably.
3.5 Function Button
The Function Button activates KSR-01IP ´s special functions Manual Function,
Factory Reset and Boot Mode. It depends on time/number/state the Function Button
is being pressed.
3.5.1 Manual Function
A rather short press (≈ 3 sec) of the Function Button activates the Manual Function
during normal operation. With a second short button press it can be deactivated
before the Manual Function Switch-off time is expired.