For calling a scene or saving a new value for the scene, you have to send the accordingly code to the 
relevant communication object for the scene: 

Scene 

Retrieve 

Save 

Hex. 

Dez. 

Hex. 

Dez. 

0x00 

0x80 

128 

0x01 

0x81 

129 

0x02 

0x82 

130 

0x03 

0x83 

131 

0x04 

0x84 

132 

0x05 

0x85 

133 

0x06 

0x86 

134 

0x07 

0x87 

135 

0x08 

0x88 

136 

10 

0x09 

0x89 

137 

11 

0x0A 

10 

0x8A 

138 

12 

0x0B 

11 

0x8B 

139 

13 

0x0C 

12 

0x8C 

140 

14 

0x0D 

13 

0x8D 

141 

15 

0x0E 

14 

0x8E 

142 

16 

0x0F 

15 

0x8F 

143 

17 

0x10 

16 

0x90 

144 

18 

0x11 

17 

0x91 

145 

19 

0x12 

18 

0x92 

146 

20 

0x13 

19 

0x93 

147 

21 

0x14 

20 

0x94 

148 

22 

0x15 

21 

0x95 

149 

23 

0x16 

22 

0x96 

150 

24 

0x17 

23 

0x97 

151 

25 

0x18 

24 

0x98 

152 

26 

0x19 

25 

0x99 

153 

27 

0x1A 

26 

0x9A 

154 

28 

0x1B 

27 

0x9B 

155 

29 

0x1C 

28 

0x9C 

156 

30 

0x1D 

29 

0x9D 

157 

31 

0x1E 

30 

0x9E 

158 

32 

0x1F 

31 

0x9F 

159 

Table 14: Calling and saving scenes 

 

 

Содержание RF-AKK1ST.01

Страница 1: ...ch Geb udeautomation Tel 49 2263 880 Fax 49 2263 4588 E Mail automation mdt de www mdtautomation de 1 01 2015 Technical Manual MDT RF Socket KNX RF RF AxK1ST 01 RF AKK1ST 01 RF Socket RF AZK1ST 01 RF...

Страница 2: ...Default settings of the communication objects 12 4 Parameter Switch Channel 13 4 1 Identical parameter 13 4 1 1 Relay operating mode 13 4 1 2 Central function 14 4 1 3 Behavior at block unblock 14 4...

Страница 3: ...GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 3 6 Index 39 6 1 List of figures 39 6 2 List of tables 39 7 Attachment 40 7 1 Statutory requirements 40 7...

Страница 4: ...mode 2 2 Verwendung Einsatzgebiete The MDT RF socket can switch almost all electrical devices The outputs can operate as normal switching outputs or as output with staircase function In both settings...

Страница 5: ...3 Aufbau Bedienung The following figure shows the design of the RF socket Figure 1 Overview Hardware RF socket The output can be switched via a short key press on the button An active output is shown...

Страница 6: ...rement the following menus are also available Active power measurement The active power measurement can send the current power of the connected load and in accordance to the value specific function su...

Страница 7: ...After wiring the allocation of the physical address and the parameterization of every channel follow 1 Connect the interface with the bus e g MDT USB interface 2 Connect parameterize and download RF L...

Страница 8: ...uator reacts to Incoming telegramm Push buttons Visu for manual control Communication object is shown at the operati g ode s itch and controls the channel On Off which is normally connected to all con...

Страница 9: ...trolli g push button for sending its current state to the push button 6 Channel A Logic 1 DPT 1 002 receive Actuator reacts to Incoming telegramm external switching state object of other devices Chan...

Страница 10: ...Visu Diagnostic Recording Communication object is shown at activated voltage measurement 11 Sub Meter Active Energy DPT 13 010 DPT 13 013 send Socket sends the active energy since the last reset Visu...

Страница 11: ...nds exceedance of voltage Visu Diagnostic A tuator Communication object is shown at voltage measurement and monitoring of voltage 18 Active power meter Lower deviation of voltage DPT 1 001 send Socket...

Страница 12: ...value 4 Byte Niedrig X X X 11 Sub Meter Active Energy 4 Byte Niedrig X X X 12 Main Meter Active Energy 4 Byte Niedrig X X X 13 Active power meter Exceedance of load 1 Bit Niedrig X X X 14 Active powe...

Страница 13: ...1 1 Relay operating mode The following illustration shows the setting options for this parameter Figure 2 Operating mode The following chart shows the dynamic range for this parameter ETS text Dynamic...

Страница 14: ...t all ha els ith a activated central function are switched on with their current parameterization So switch on delays or staircase functions are still kept The central function can make programming mu...

Страница 15: ...o available for the Beha ior he u lo ked This a tio is alled he the lo ki g fu tio is dea ti ated again The following chart shows the corresponding communication object Number Name Length Usage 3 Bloc...

Страница 16: ...4 2 Switching output The following parameters which are described at the headings 4 3 x are only available at channels selected as switch 4 2 1 Overview By choosing a channel as switch a sub menu cal...

Страница 17: ...annel in seconds Central function not active active Activates the central function for this channel Behavior when locked Off On no change Action for activating the blocking process Behavior when unloc...

Страница 18: ...delayed switch of the channel At sending an on signal to the channel first the adjusted on delay time expires and afterwards the channel will be switched on The off delay works on the same principle...

Страница 19: ...ND function and an OR function The following figure shows an overview of the basic logic function with two objects Figure 8 Overview Logic function The logic function consists of the activated input o...

Страница 20: ...following table illustrates the two logic functions AND Connection OR Connection Switch On Off Logic 1 Logic 2 Channel switched Switch On Off Logic 1 Logic 2 Channel switched 0 0 0 Nein 0 0 0 Nein 0 0...

Страница 21: ...w sub menu for the scenes appears at the left drop down menu There are settings to activate single scenes set values and scene numbers and switch the memory function on off at this sub menu Scenes are...

Страница 22: ...GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 22 There are up to 8 storage options for scenes at every channel These 8 storage options can get any of th...

Страница 23: ...value 1 less than the adjusted scene number Scene C Off On Activation of the scene C Scene number C 1 64 1 Scene number Calling value 1 less than the adjusted scene number Scene D Off On Activation of...

Страница 24: ...3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x8A 138 12 0x0B 11 0x8B 139 13 0x0C 12 0x8C 140 14 0x0D 13 0x8D 141...

Страница 25: ...oth communication objects for the scenes to the same group address By sending the calling value both scenes are called Your programming can become much clearer if you divide your group addresses by sc...

Страница 26: ...26 4 3 Staircase The following parameters which are described at the headings 4 4 x are only available at channels selected as staircase 4 3 1 Overview By choosing a channel as staircase a sub menu c...

Страница 27: ...when warning is activated Prewarning time s sec 120 sec Adjustment how long the light shall be switched on after the warning Whole duration of the warning process is the sum of the 3 times Staircase...

Страница 28: ...r off of the ha el after a adjusted ti e alled ti e for stair ase The ti e for stair ase a e para eterized freely By se di g a o sig al at the o u i atio o je t the channel is switched on and the time...

Страница 29: ...an almost out and the lights are switched off soon This warning happens trough a short turn off the lights The duration of the turn off is indicated by the warning time A value of 1 3s is advisable fo...

Страница 30: ...witching the staircase function have a look atTable 16 Communication object staircase When this function is not activated the channel switches only off after the staircase time runs out 4 3 5 Extend s...

Страница 31: ...2263 880 Fax 49 2263 4588 knx mdt de www mdt de 31 5 Parameter Measurement The following parameters are only in the RF socket with active power meter RF AZK1ST 01 available 5 1 Active power measuremen...

Страница 32: ...n for exceedance deviating Hysteresis in 10 100 10 defines the hysteresis Behavior at exceeding deviating send nothing send ON telegram send OFF telegram send ON telegram and channel OFF send OFF tele...

Страница 33: ...s of 10 and a value for underrun of 100W causes an active lower deviation of load at 100W which is released until the value exceeds 110W again The retention time by exceedance deviating specifies how...

Страница 34: ...surement The following table shows the available settings ETS text Dynamic range default value comment General Settings Object selection Value in mA DPT7 012 Floating value in mA DPT9 021 Floating val...

Страница 35: ...tched off Behavior at not exceeding deviating send nothing send ON telegram send OFF telegram send ON telegram and channel OFF send OFF telegram and channel OFF defines the action for exceedance devia...

Страница 36: ...ollowing figure shows the menu voltage measurement Figure 19 Menu voltage measurement The following table shows the available settings ETS text Dynamic range default value comment General Settings Sen...

Страница 37: ...d off Behavior at not exceeding deviating send nothing send ON telegram send OFF telegram send ON telegram and channel OFF send OFF telegram and channel OFF defines the action for exceedance deviating...

Страница 38: ...meter Send value of sub meter cyclic no send 5min 24h no send defines the sending behavior of the sub meter Behavior after bus power return no reset reset sub meter reset main and sub meter defines th...

Страница 39: ...ent 36 Figure 20 Menu meter 38 6 2 List of tables Table 1 Communication objects switching output 9 Table 2 Overview objects Measurement 11 Table 3 Communication objects default settings 12 Table 4 Ope...

Страница 40: ...ur danger for humans animals or material assets Do not let the packaging lying around careless plastic foil bags etc can be a dangerous toy for kids 7 2 Routine disposal Do not throw the waste equipme...

Страница 41: ...Line Coupler If the mains voltage fails all outputs were switched off After mains voltage recovery the relay position will be restored The MDT KNX RF Switch Actuator must be installed in dry rooms Fo...

Страница 42: ...compensated 800W 800W Fluorescent lamps parallel comp 180W 180W Max number of electronic transformers 3 3 Output life expectancy mechanical 1 000 000 1 000 000 Permitted wire gauge KNX busconnection t...

Отзывы: