Settings for current monitoring(adjustable for exceeding and underflow):
Value for exceedance/lower
deviation of load
0 - 16000
defines the threshold for triggering an
action for exceedance/deviating
Hysteresis in %
10-100%
[10%]
defines the hysteresis
Behavior at
exceeding/deviating
send nothing
send ON-telegram
send OFF-telegram
send ON-telegram and
channel OFF
send OFF-telegram and
channel OFF
defines the action for
exceedance/deviating of the set
threshold:
Send ON/OFF telegram:
The object
sends the adjusted telegram.
Send ON/OFF telegram and channel
OFF:
The object sends the adjusted
telegram and the channel is switched
off
Behavior at not
exceeding/deviating
send nothing
send ON-telegram
send OFF-telegram
send ON-telegram and
channel OFF
send OFF-telegram and
channel OFF
defines the action for
exceedance/deviating of the adjusted
threshold; description see before
Send cyclic
no send, 5min-24h
[no send]
The telegram for exceedance/deviating
is sent cyclic
Retention time by
exceedance/deviating in sec.
0-30000
[0]
defines a retention time, which must
run out at an exceedance/deviating
before a telegram is sent
Table 19: Menu current measurement
The behavior of the hysteresis and the retention time is described in detail in 5.1 Active power
measurement.
The following table shows the available communication objects:
Number
Name
Length
Usage
9
Current value
2 Byte/
4 Byte
Sending the measured current value
15
Exceedance of current
1 Bit
Sending an exceedance of load
16
Lower deviation of
current
1 Bit
Sending a deviation of load
Table 20: Communication objects current measurement