Technical Data
RF-AKK1ST.01
RF-AZK1ST.01
Current measurement range
--
10mA - 20A
Measuring inaccuracy
--
2%
Sampling rate
--
2000 samples/500ms
Transmitter frequency
868,3MHz (For operating inside the EU)
868,3MHz (For operating inside the EU)
Range
150m
150m
Output level
10dBm
10dBm
Sensitivity
>-105dBm
>-105dBm
Compatibility
KNX RF S-Mode (with ETS5 support)
KNX RF S-Mode (with ETS5 support)
Output switching ratings
Ohmic load
16A
16A
Capacitive load
21uF
21uF
Voltage
230VAC
230VAC
Maximum inrush current
80A/150µs
40A/600µs
80A/150µs
40A/600µs
Maximum load
Incandescent lamps
2300W
2300W
Halogen lamps 230V
2000W
2000W
Halogen lamps, electronic transformer
800W
800W
Fluorescent lamps, not compensated
800W
800W
Fluorescent lamps, parallel comp.
180W
180W
Max. number of electronic transformers
3
3
Output life expectancy (mechanical)
1.000.000
1.000.000
Permitted wire gauge
KNX busconnection terminal
0,8mm Ø, solid core
0,8mm Ø, solid core
Power supply
230VAC/50Hz
230VAC/50Hz
Power consumption mains 230VAC typ.
< 0,3
< 0,3W
Operation temperature range
0 to + 45°C
0 to + 45°C
Enclosure
IP 20
IP 20
KNX RF+ Socket
EU Declaration of Conirmity Socket RF+
Hereby, MDT technologies GmbH declares that the radio equipment type radio RF-AxK1ST.01 is in compliance with
directive 2014/53/EU. The full text of the EU declaration of conirmity is available at the following internet address:
www.mdt.de/download/MDT_CE_RFAKK.pdf
MDT technologies GmbH
•
51766 Engelskirchen
•
Papiermühle 1
Tel.: + 49 - 2263 - 880
•
Fax: + 49 - 2263 - 4588
•
•
www.mdt.de
Stand: 0716
DIN EN ISO 9001
TAW Cert
Zert.Nr.1905606
N